Appendix A: Configuration presets
84
SynaG Series Installation Manual
NBN S 21-100
Table 55: Configuration presets
Preset Control
panel
EOL type
Output
type
Warning
sounder
outputs
Evacuation
sounder
outputs
Zone type
21 Four-zone,
eight-zone
Passive
Class B
2
2
Odd: Automatic
Even: Manual
22 Four-zone,
eight-zone
Passive,
CleanMe
enabled [1]
Class B
2
2
Odd: Automatic
Even: Manual
21 Four-zone,
eight-zone
EN 54-13
supervision
Class A
1
1
Odd: Automatic
Even: Manual
[1] The CleanMe feature is available only with Aritech detectors.
Table 56: Additional configuration characteristics
Default sounder delay
0 minutes
Default zone delay
ON
Start/Restart sounders
Start sounders or restart stopped sounders at user level 2 with
or without a fire alarm event
Table 57: Inputs and outputs
Input/Output Standard
EN
54-13
INPUT1
Remote reset
Remote reset
INPUT2
Delays off
Delays off
OUT1 Evacuation
sounders
Evacuation sounders
OUT2 Evacuation
sounders
OUT3 Warning
sounders
Warning sounders
OUT4 Warning
sounders
Note: Two-zone control panels have only two outputs with EN 54-13 disabled (OUT1 and OUT2)
or a single output with EN 54-13 enabled (OUT1/2).
Summary of Contents for Kidde AirSense SynaG Series
Page 1: ...SynaG Series Installation Manual P N 501 435003 1 10 REV 1 0 ISS 14OCT11 ...
Page 6: ...iv SynaG Series Installation Manual ...
Page 10: ...Chapter 1 Introduction 4 SynaG Series Installation Manual ...
Page 72: ...Chapter 4 Maintenance 66 SynaG Series Installation Manual ...
Page 84: ...Chapter 5 Technical specifications 78 SynaG Series Installation Manual ...
Page 96: ...Appendix A Configuration presets 90 SynaG Series Installation Manual ...
Page 100: ...Appendix B Product compliance 94 SynaG Series Installation Manual ...
Page 103: ......
Page 104: ......