background image

WS4916 Series Wireless Smoke Detector

Installation and Operating Instructions

Read this instruction sheet thoroughly before installation and use of the WS4916 Wireless Smoke Detector

Introduction

The WS4916 is a wireless photoelectric smoke detector with a fixed
temperature and rate of rise heat detector, and an internal piezo-
electric alarm. Four versions are available: US version (UL), Canadian
version (ULC), International version (EU), and Australian version
(AUS).

NOTE:

Heat detection based on rate of rise has not been investi-

gated by UL/ULC.

NOTE:

Australian version does not include the heat detector.

Operation

Approximately every 7 to 8 seconds the unit tests for a smoke or
heat alarm condition. During this sequence the unit also performs
self diagnostics, and checks for tampers and faults. During normal
operation the LED will flash every 50 seconds and the sounder will
not sound.

Smoke Alarm

The smoke detector will go into alarm when the signal level exceeds
the “alarm” threshold and automatically restore when the signal
level falls below the alarm “restore” threshold. During an alarm the
LED will flash 1/second and the sounder will sound the evacuation
temporal pattern (UL, EU) or continuous beeps (ULC).
The smoke detector has a preset warning threshold at 75% of the
alarm threshold. If the signal level stays above this threshold, but
below the alarm threshold, for more than 120 seconds, the detec-
tor will go into the “warning” state. If the signal level falls below
the early warning “restore” threshold, the detector will restore to its
normal state automatically. If the signal level rises above the alarm
threshold, the detector will go into alarm. The LED will flash and the
sounder will chirp every 50 seconds when in the warning state.

NOTE:

This feature is intended to provide a warning if the envi-

ronment is persistently close to the alarm threshold and provide
more time to investigate and either escape or correct the situa-
tion.

Smoke - Drift Compensation

The detector automatically compensates for long-term environmen-
tally induced changes to maintain a constant smoke sensitivity.
When the drift compensation has reached its high or low limit of
adjustment, the detector will go into the trouble state.

Heat Alarm

The heat detector will go into alarm when the heat signal level
exceeds the heat alarm threshold (135ºF/57ºC); and will automati-
cally restore when the heat signal level falls below the heat alarm
threshold (restore). The detector will also go into heat alarm if there
is a rapid increase in the temperature over a short period of time.
During an alarm the LED will flash 1/second and the sounder will
sound the evacuation temporal pattern (UL, EU) or continuous
beeps (ULC).

Tamper

The removal of the detector from the mounting plate initiates a
“tamper” transmission. The tamper condition is restored after the
detector is mounted on the plate.

Wireless Transmissions

A supervisory message is transmitted at 64 minute intervals (12
minutes in EU model) to the control panel. If the signal is not
received the control panel determines that the detector is missing.
The detector transmits the following:

Alarm / Alarm Restore

- (heat or smoke alarm). Transmitted at

time of occurrence.

Tamper / Tamper Restore

- (tamper switch activated) 10 second

maximum delay on restore before transmission.

Low Battery

- (battery voltage falls below threshold). The bat-

teries are tested & transmitted at the time of a supervisory or
other transmissions.

Trouble

- (detector fault or sensor compensation limit reached).

Troubles are transmitted at the time of occurrence (one trouble
per supervisory interval).

Batteries

The WS4916 is powered by two, 3V

DC

lithium batteries.

Do NOT use batteries other than those listed.

The low battery threshold is set so the batteries will provide not less
than 14 days of operation and at that point the detector will send a
“low battery” signal. If the battery is still low 7 days after falling
through the low battery threshold, the horn will “chirp” once every
48 seconds until battery failure. During the first 7 days after low
battery detection, (non-chirp period), if the detector is tested or
goes into alarm, the horn will “chirp” once the test or alarm is
restored and remain “chirping” until battery failure.
Replacement batteries can be purchased from the distributor, the
installation company, hardware stores or supermarkets etc.

Installation Instructions
Installation

The WS4916 Series wireless smoke detector shall be installed and
used within an environment that provides the pollution degree max
2 and overvoltages category II in NON HAZARDOUS LOCATIONS,
indoor only. The equipment is designed to be installed by SERVICE
PERSONS only; (SERVICE PERSON is defined as a person having the
appropriate technical training and experience necessary to be aware
of hazards to which that person may be exposed in performing a
task and of measures to minimize the risks to that person or other
persons.)

1. Smoke Detector Placement

On smooth ceilings, detectors may be spaced 9.1m (30 feet) apart
as a guide. Other spacing may be required depending on ceiling
height, air movement, the presence of joists, uninsulated ceilings,
etc. Consult National Fire Alarm Code NFPA 72 Chapter 11, CAN/
ULC-S553-02 or other appropriate national standards for installa-
tion recommendations.

• Do

NOT

locate smoke detectors at the top of peaked or gabled

ceilings; the dead air space in these locations may prevent the unit
from detecting smoke. Avoid areas with turbulent air flow, such
as near doors, fans or windows. Rapid air movement around the
detector may prevent smoke from entering the unit.

• Do

NOT

locate detectors in areas of high humidity.

• Do

NOT

locate detectors in areas where the temperature rises

above 38ºC (100ºF) or falls below 5ºC (41ºF).

Install Smoke detectors in accordance with NFPA 72, Chapter 11.

“Smoke detectors shall be installed outside of each sleeping area in
the immediate vicinity of the bedrooms and on each additional
story of the family living unit, including basements and excluding
crawl spaces and unfinished attics. In new construction, a smoke
detector also shall be installed in each sleeping room.”

LED/Test Button

Piezo Siren

Alignment Marks

'*

Summary of Contents for WS4916 Series

Page 1: ... the control panel If the signal is not received the control panel determines that the detector is missing The detector transmits the following Alarm Alarm Restore heat or smoke alarm Transmitted at time of occurrence Tamper Tamper Restore tamper switch activated 10 second maximum delay on restore before transmission Low Battery battery voltage falls below threshold The bat teries are tested trans...

Page 2: ...The central monitoring station if used should be notified prior to the test being generated This will prevent a false alarm and an unnecessary response from the central monitoring station Initiate test by pressing the test button for 5 seconds minimum Alarm activation is indicated by the flashing LED the sounder and transmission of the alarm signal to the control panel The detector restores to nor...

Page 3: ...e sounder makes clicking noises during this time Press the button until the unit alarm sounds an alarm should be sent to the control panel When the button is released the alarm should cease If this does not occur ensure batteries are the correct type in good condi tion and are installed correctly see 3 Install Batteries in the Installation Instructions section Upon completing the functional testin...

Page 4: ...DUCT but You may only have one copy per license installed at any given time You may use the back up copy solely for archival purposes Except as expressly provided in this EULA You may not otherwise make copies of the SOFT WARE PRODUCT including the printed materials accompanying the SOFTWARE 2 DESCRIPTION OF OTHER RIGHTS AND LIMITATIONS a Limitations on Reverse Engineering Decompilation and Disass...

Page 5: ...n Wird das Signal nicht empfangen so geht die Alarmzentrale davon aus dass der Melder fehlt Der Melder überträgt Alarm Alarm Rückstellung Wärme oder Rauchalarm Übertragung zum Zeitpunkt des Auftretens Sabotage Sabotage Rückstellung Sabotagekontakt aktiviert 10 Sekunden maximale Verzögerung zur Rückstellung vor Übertragung Batterien erschöpft Batterienspannung fällt unter den Grenzwert Der Batterie...

Page 6: ...ende LED Sirene und Übertragung des Alarmsignals an die Alarmzentrale angezeigt Der Melder stellt sich zurück wenn Sie den Testknopf loslassen HINWEIS Gewähren Sie dem Melder wenigstens 20 Sekunden um wieder zu aktivieren und sich zurückzustellen Benutzen Sie den Testknopf nicht wenn Sie Rauch wahrnehmen HINWEIS Befindet sich der Melder während des Tests in einem der folgenden Zustände so löst er ...

Page 7: ...hnitt Installationsanleitung Nach dem Funktionstest des Rauchmelders überprüfen Sie die Messkammer des Geräts auf korrekten Betrieb Zum Testen der Messkammer schwenken Sie einen brennenden Baumwolldocht oder ein Räucherstäbchen außen am Gerät bis eine gewissen Menge Rauch in die Messkammer eintritt oder Alarm ausgelöst wird Funktioniert der Rauchmelder nicht korrekt so wenden Sie sich bitte an Ihr...

Page 8: ... anderen nicht zur Verfügung stellen oder es auf einem Server oder einer Website einstellen e Übertragung des Softwareprodukts Sie dürfen all Ihre Rechte unter dieser Endverbraucher Lizenzvereinbarung nur als Teil eines permanenten Verkaufs oder einer Übertragung der HARDWARE übertragen vorausgesetzt dass Sie keine Kopien behalten Sie das gesamte SOFTWAREPRODUKT einschließlich allen Komponenten Me...

Reviews: