4
SETTINGS AND CALIBRATIONS
64
Chapter
4
SETTINGS
AND CALIBRATIONS
■
Waveform Comparison Setting
Set the waveform comparison function by Wave Comparison Setting. Set each item according to
the setting order. Skip unnecessary setting items.
Operation
Main screen
→
Setting
→
Work Setting
→
Wave Setting (
→
Next
→
Next)
1.
Registration of Reference Waveform.
Input and register reference waveform(s).
Operation
Main screen
→
Setting
→
Work Setting
→
Wave Setting
→
Reference Wave
①
Not to use the currently-registered waveform(s), press
, and select
.
②
Satisfy the Measurement Start Condition, and start measurement.
③
Satisfy the Measurement Stop Condition, and stop measurement.
④
A measurement waveform is displayed.
Now, to delete the measurement waveform, press
, and
select .