Document No: LT0117
F4000 LCD Operator's Manual
Operating Instructions - Zone Functions
Issue 2.38
19 April 2002
Page 7-17
7.5.5 NOTES
(a)
Multiple zones can be set to "AUTO-RESET" mode at the same time.
(b)
"AUTO-RESET" mode cannot be entered if there is any Zone, Ancillary, Automatic,
System, or Battery Test in progress.
(c)
If any zone is in "AUTO-RESET" mode then it is not possible to perform a Zone,
Ancillary, System or Battery Test.
(d)
All programmed input time delays (e.g. alarm verification) are overridden to allow the
basic operation of the detectors to be easily tested.
(e)
The internal sounder is not operated by a zone in "AUTO-RESET" mode.
(f)
A zone in "AUTO-RESET" mode will automatically return to normal operation after
ONE HOUR from the last alarm received. However no reset signal is applied to the
alarm zone circuits.
(g)
Isolating the Zone - should be used to exit the test if the alarm LED is still flashing to
prevent inadvertent signalling of alarms to the brigade.
(h)
Pressing global "RESET" or "ISOLATE" keys and resetting of zones not under test,
will not affect any of the zones or circuits in Auto-Reset mode.
(i)
This test is similar to the New Zealand FP4 and FP4000 fire alarms non-latching
mode, except that with F4000 only the selected zones are in Auto Reset test mode.
All other zones function normally.