9.2
MAINS ISOLATE SWITCH
To switch the F4000 LCD FIP panel ON or OFF, first open the front protective door and the
inner display door.
The "MAINS ISOLATE SWITCH" is located at the top left hand side of the cabinet rear, to
the left of the mains transformer.
This switch controls the mains power supply to the panel, including the battery charger.
The normal position of this switch is ON, and it should only be turned OFF (ie MAINS
ISOLATED), when testing that the FIP will run on batteries, or by maintenance personnel.
NOTE:
The Battery is not disconnected by the "MAINS ISOLATE SWITCH".
9.3 POWER
UP
To place a correctly installed F4000 LCD FIP into operation, perform the following steps:
STEP 1
Ensure that the Mains Isolate Switch is OFF.
STEP 2
Ensure that 240 VAC is available to the panel from the mains distribution
switchboard.
STEP 3
Turn the Mains Isolate Switch ON.
STEP 4
For a New Zealand mode FIP the "NORMAL" LED should be off and the "FIRE"
LED should be flashing. The "CHGR/BATT FAULT" and "DEFECT" LEDs should
also be flashing.
Pressing the "ACK" key followed by the "RESET" key should turn off the "FIRE"
and "CHGR/BATT FAULT" LEDs. The "DEFECT" LED should remain flashing.
STEP 5
Check that the keyboard green "MAINS ON" LED indicator is illuminated.
The LCD should be displaying the a "Powering Up" message, the time and date
and any programmed system name.
Wait until the "Powering Up" message is replaced by the software version number.
For a New Zealand mode F4000, the "NORMAL" LED should be ON flashing, and
the "DEFECT" LED should be OFF. Note that if Battery Disconnect monitoring is
enabled, there will be a Battery Disconnect fault present until the batteries are
connected.
STEP 6
Perform a System Test.
STEP 7
Install Batteries.
STEP 8
Perform a Battery Test.
If Battery Test fails; check battery connections; if battery flat, leave for 24 hours
and retest.