Document No: LT0117
F4000 LCD Operator's Manual
Operating Instructions - Zone Functions
Issue 2.38
19 April 2002
Page 7-13
7.4
ZONE OR ANCILLARY RESET
7.4.1 FUNCTION
A Zone Reset command performs the following functions:
(a)
For Alarm Zones:
-
Resets all circuits mapped to the selected zone.
-
Clears ALARM and FAULT conditions and indications.
-
Silences the alarm and fault sounder, if no other alarms or faults exist.
-
Removes the Zone from Zone Test.
-
Returns the Zone from Auto-Reset mode to normal operation.
(b)
For Ancillary Control Zones:
-
Resets any latched "FLT" indicator associated with the selected ancillary
control zone.
7.4.2 OPERATING SEQUENCE – SINGLE ZONE
From zone recall displays, to reset the displayed zone, press:
-
The LCD will query if this is the zone to be RESET. Press "ACK" to
reset, or "CLEAR" to abort.
From all other information displays, or the base display, press:
to reset zone number n n n. A networked zone may also be reset – refer Section 2.5.1 for
networked zone numbering.
-
Any red alarm indicators that were steady or flashing will be turned
OFF and the alarm circuit(s) reset.
-
Any amber fault indicators that were showing will be turned OFF.