F4000 LCD Operator's Manual
Document No: LT0117
FFCIF Type 2 Fire Fighters Guide
Page C-2
19 April 2002
Issue 2.38
FIRE FIGHTERS GUIDE - FFCIF TYPE 2
1.
ACKNOWLEDGING ALARMS
Press "ACK" key once.
-
The local sounder will silence but the alarm bells will continue to ring.
Press Bells Isolate, if required, to stop the bells ringing.
2.
RESET/ACKNOWLEDGE ALL ZONES IN ALARM
Press "RESET" key once.
-
Flashing/Steady "ALM" LEDs -> OFF
-
The LCD will display "No more events in alarm list"
-
Any new alarm will cause the bells to ring again and the appropriate
zone alarm LED to flash.
3.
ISOLATE/ACKNOWLEDGE ALL ZONES IN ALARM
Press "ISOL" key once.
-
Flashing "ALM" LEDs -> STEADY
-
Alarm Zones "ISO" LEDs -> STEADY
-
The LCD will display "No more events in alarm list"
4.
VIEW/ACKNOWLEDGE/RESET/ISOLATE
Press the Recall key once.
-
The LCD display changes to Type 3 FFCIF mode, which allows
individual acknowledgement, reset and isolation of each alarm.
-
To change the LCD display to Type 2 FFCIF Global
Acknowledgement, Reset and Isolation control, press the RECALL
key again.