F4000 LCD Operator's Manual
Document No: LT0117
Operating Instructions - Point Functions
Page 8-12
19 April 2002
Issue 2.38
8.3.2 OPERATING
SEQUENCE
From the point recall display for the specified point, press:
From the base display or any other information display, press:
where rrr is the responder number (1-127)
ppp is the analogue point number (1-200)
The FIP will check to see that the point rrr.ppp is in fact an addressable detector for which
the alarm or pre-alarm sensitivity can be changed.
The LCD will display the point number and type, and prompt for viewing of or changes to the
pre-alarm or alarm sensitivity. Press:
To view or set Pre Alarm sensitivity, or
To view or set the Alarm sensitivity.
The LCD then displays the point number and type, along with current setting for the selected
sensitivity, and prompts for a new setting.
The current setting is displayed in the form "t sss uuu" where:
t =
D - Default sensitivity
A - Alternative sensitivity
I - Individual sensitivity
sss = the sensitivity setting.
uuu = the appropriate units (MICX, %/m, Deg C).