4. Periodic Test by Installer Code
D-306488 WK250 Installer’s Guide
77
4. Periodic Test by Installer Code
4.1 General Guidance
This mode provides you with the means to conduct a periodic test, via the "
PERIODIC TEST
" menu, at least once a
week and after an alarm event.
When you are instructed to perform a periodic test, walk throughout the site to check the detectors / sensors (except for
Sirens and Temperature Sensors). When a detector/sensor is triggered into alarm, its name, number and the alarm
reception level should be indicated (for example, "
Bathroom
", "
Z19 strong
") and the buzzer should sound according to
the alarm reception level (1 of 3). Each device should be tested according to the device Installation Instructions.
To enter the "
PERIODIC TEST
" menu and to conduct a periodic test, proceed as follows:
Step 1
Step 2
READY
[1]
Select the test to be performed
[2]
PERIODIC TEST
SIRENS TEST
(enter installer / master
code)
TEMPERATURE TEST
TEST ALL DEVICES
TEST ONE DEVICE
<OK> to Exit
– Periodic Test
[1]
Not including Siren and Temperature Sensors
[2]
After reviewing all untested devices the WK250 will read "
<OK> TO END
". You can now do one of the following:
press
to abort the testing procedure; press
to continue the testing procedure; or press
to
exit the testing procedure.
4.2 Conducting a Periodic Test
The WK250 enables you to conduct the periodic test in four parts:
Siren Test
: Each siren of the system is automatically activated for 3 seconds (outdoor sirens with low volume).
Temperature Sensor Test:
When Temperature Sensors are enrolled in the system, the WK250 displays the
temperature of each zone in Celsius or Fahrenheit.
Test all devices:
All devices are tested.
Other Device Test:
Each of the other devices in the system is activated by the installer and the display indicates which
devices were not yet tested. The "
it's me"
indication helps to identify the untested devices if necessary. A counter also
indicates the number of devices that remain untested.
READY
⋅⋅⋅
PERIODIC TEST
⋅⋅⋅
MENU you wish
To conduct a periodic test, make sure the system is disarmed and then enter the "
PERIODIC TEST
" menu using your
installer code (8888 by default) or master installer code (9999 by default). Immediately after entering the
"
PERIODIC TEST
" menu, all 4 LEDs on the panel and all 5 LEDs on the WK250 keypad will momentarily light (LED
test).
Option
Instructions