3. Programming
D-306488 WK250 Installer’s Guide
31
Option and default
Configuration Instructions
2. It is recommended that crossed zones will be only zones used for detection of
burglary i.e. "Zone Types": Entry/ Exit, Interior, Perimeter and Perimeter follower.
3. If a cross zone is in Soak Test mode, then each zone of this zone couple functions
independently.
Important!
Do not define "cross zoning" to any other zone types such as Fire,
Emergency, 24h audible, 24h silent etc.
3.5.4 Configuring Alarms & Troubles
The following table provides you with a detailed description of each option and its configuration settings. To select an
option and change its configuration – refer to section 3.5.1.
Option and default
Configuration Instructions
31:PANIC ALARM
audible
Define whether or not the user will be allowed to initiate a Panic Alarm from keypads (by
simultaneous pressing the two "Panic Buttons") or keyfobs (by simultaneous pressing the
"Away" + "Home" buttons) and whether the alarm will be "silent" (i.e. only reporting of the
event) or also audible (i.e. the sirens will also sound).
Options:
audible
;
silent
and
disabled
.
Note:
If the BS8243 or DD243 setup is selected in Operation Mode (see section 3.14),
Panic Alarm must be set to “disabled” (applicable in UK panels only).
32:DURESS ALARM
CODE 2580
A duress (ambush) alarm message can be sent to the Monitoring Station if the user is
forced to disarm the system under violence or menace. To initiate a duress message, the
user must disarm the system using a duress code (2580 by default).
(not applicable in UK)
To change the code, enter the new 4-digit of the new Duress code at the position of the
blinking cursor or enter 0000 to disable the duress function and then press
.
Note:
The system does not allow programming a duress code identical to an existing user
code.
33:INACTIVE ALRT
disabled
If no sensor detects movement in interior zones at least once within the defined time
window, an
“inactive alert"
event is initiated.
Define the
time window
for monitoring the
lack of motion
.
Previously known as
"NOT ACTIVE"
Options:
disabled
;
after
3/6/12/24/48/72 hours
34:TAMPER ALARM
active
Define whether the Tamper switch protection of all zones and other peripheral devices
(except the control panel) are "
active
" or "
not active
".
Warning!
: If you select "
not active", be aware that no alarm or report will be initiated in
case of tampering with any of the system peripheral devices.
35:AC FAIL REPRT
after 5 minutes
To avoid nuisance reporting in case of short interruptions in the house of AC power, the
system reports an AC Fail message only if the AC power does not resume within a pre-
determined time delay.