29
2020/09
Approvals and tests
5.2.3
Technical data for the push-in tension clamp terminals
Designation
Approvals
CE
cULus
Tests (EN 61131-2)
Cold
DIN IEC 68-2-1, Temperature -25 °C/185 °F, duration
96 h; device not in use
Dry heat
DIN IEC 68-2-2, Tempe85 °C/185 °F, dura
-
tion 96 h; device not in use
Damp heat, cyclic
DIN IEC 68-2-30, tempe55 °C/131 °F, dura
-
tion 2 cycles every 12 h; device in use
Pollution severity according to IEC 664 (EN 61 131-2)
2
Protection to IEC 529/EN 60529
IP20 (not evaluated by UL)
MTTF
224 years according to SN 29500 (Ed. 99) 20 °C
Designation
Protection class
IP20 (not evaluated by UL)
Insulation stripping length
8 mm + 1 mm/0.32 inch + 0.039 inch
Max. wire range
0.14…1.5 mm
2
/0.0002…0.0023 inch
2
/
26…16 AWG
Crimpable wire
"e” solid core H 07V-U
0.14…1.5 mm
2
/0.0002…0.0023 inch
2
/
26…16 AWG
"f” flexible core H 07V-K
0,5…1,5 mm
2
/0.0008…0.0023 inch
2
/
25…16 AWG
"f” with ferrules according to
DIN 46 228/1 (ferrules crimped gas-tight)
0.25…1.5 mm
2
/0.0004…0.0023 inch
2
/
30…16 AWG