47
2020/09
BL20-2AI-THERMO-PI
(2 byte parameters per channel)
BL20-4AI-U/I (1 byte parameters per channel)
Byte
Bit
Parameter name
Value
0/1
0
Mains suppression
0 = 50 Hz
0 = 60 Hz
1
value representation
0 = Integer (15 bit + sign)
1 = 12 bit (left-justified)
2
Diagnostic
0 = release
1 = block
3
Channel
0 = activate
1 = deactivate
7
to 4
Element
0000 = Type K, -270…1370 °C
0001 = Type B, +100….1820 °C
0010 = Type E, -270…1000 °C
0011 = Type J, -210…1200 °C
0100 = Type N, -270…1300 °C
0101 = Type R, -50…1760 °C
0110 = Type S, -50…1540 °C
0111 = Type T, -270…400 °C
1000 = ±50 mV
1001 = ±100 mV
1010 = ±500 mV
1011 = ±1000 mV
… = reserved
Byte
Bit
Parameter name
Value
0 to 3
0
range
0 = 0…10 V/0…20 mA
1 = -10…+10 V/4…20 mA
1
value representation
0 = Integer (15 bit + sign)
1 = 12 bit (left-justified)
2
Diagnostic
0 = release
1 = block
3
Channel
0 = activate
1 = deactivate
4
Operation mode
0 = voltage
1 = current