89
2020/09
7.2
Integration of the RS485/422-module
7.2.1
Data image
Process input data (PZDE)
The BL××-1RS485/422-module sends the data, received by the device, into a 128-byte receive-buf
-
fer. The module then transmits the data segmented via the module bus and the gateway to the SPS.
The transmission is realized in a 8-byte format which is structured as follows:
6 bytes are used to contain the user data.
1 byte contains the diagnostics data.
1 status byte is required to ensure trouble-free transmission of the data.
Meaning of the data bits (process input)
Fig. 31: Process input data SPS
Designation
Value
Description
BufOvfl; Fra
-
meErr; Hnd
-
ShErr; HwFail
-
ure; PrmErr
0 - 255
Diagnostic information (correspond to the diagnostic information in the
diagnosis telegram).
These diagnostics are always displayed and independent to the setting of
the parameter „Diagnostics".
STAT
0-1
1 The communication with the data terminal equipment (DTE) is not dis
-
turbed.
0 The communication with the data terminal equipment (DTE) is dis
-
turbed. A diagnosis message is generated if the parameter "Diagnostics" is
set to "0" = release.
The diagnostic data show the cause of the communication disturbance.
The user has to set back this bit in the process output data by using
STATRES.
TX_CNT_ACK
0-3
The value TX_CNT_ACK is a copy of the value TX_CNT. The value TX_CNT
was transferred together with the last data segment of the process output
data.
The value TX_CNT_ACK is a confirmation of successful acceptance of the
data segment using TX_CNT.