Integration of the technology modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
90
Process output data (PZDA)
The data received from the PLC are loaded into a transmit-buffer in the BL××-1RS485/422 module.
The fieldbus specific transmission for EtherCAT is realized in a 8-byte format which is structured as
follows:
6 bytes are used to contain the user data.
1 byte contains, signals to start the flushing of transmit- and receive buffer.
1 control byte is required to ensure trouble-free transmission of the data.
Meaning of the data bits (process output)
RX_CNT
0-3
This value is transferred together with every data segment. The RX_CNT
values are sequential: The RX_CNT values are sequential:
00
01
10
11
00…
(decimal: 0
1
2
3
0…)
Errors in this sequence show the loss of data segments.
RX_BYTE_
CNT
0-7
Number of the valid bytes in this data segment. In EtherCAT, the data seg
-
ments contain a maximum number of 6 bytes of user data.
Fig. 32: Process output data SPS
Designation
Value
Description
RXBUF FLUSH
0 - 1
The RXBUF FLUSH bit is used for clearing the receive buffer.
If STATRES = 0, 1 or 0
1:
A request with RXBUF FLUSH = 1 will be ignored.
If RXBUF FLUSH = 1, a rising edge 1
0 at STATRES clears the transmit buf
-
fer.
TXBUF FLUSH
0 -1
The TXBUF FLUSH bit is used for clearing the transmit buffer.
If STATRES = 0, 1 or 0
1:
A request with TXBUF FLUSH = 1 will be ignored.
If TXBUF FLUSH = 1, a falling edge 1
0 at STATRES clears the transmit buf
-
fer.
Designation
Value
Description
Summary of Contents for 6827380
Page 1: ...Your Global Automation Partner BL20 E GW EC ECO Gateway for EtherCAT Instructions for Use...
Page 2: ...2 Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com...
Page 6: ...Hans Turck GmbH Co KG T 49 208 4952 0 F 49 208 4952 264 more turck com www turck com 4...