Integration of the technology modules
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | [email protected] | www.turck.com
102
U
SWERR
Voltage U
SW
Voltage fault in U
SW
, voltage (17 VDC) for supplying the SWIRE slaves
0
OK
No error present.
1
under voltage
An error is present.
GENE-RAL
ERR
Error message
The creation of a function block shows that systems/function blocks for the general checking
of a slave for any diagnostics messages present only check the first byte.
0
none
No diagnostics message present
1
present
One/several diagnostics messages present
Byte 2
SD
ERR
Communication SWIRE slave
If the parameter SD
ERR
A is set for group diagnostics, this bit indicates an error as soon as only
one slave on the bus sets its SD error bit.
0
OK
No error is present or diagnostics function has been deacti
-
vated via the parameter setting.
1
faulty
An error is present.
PKZ
ERR
Overcurrent protective circuit-breaker
If the parameter PKZ
ERR
A is set for group diagnostics, this bit indicates an error as soon as only
one PKZ of a slave has tripped.
0
OK
No PKZ error is present or diagnostics function has been
deactivated via the parameter setting.
1
tripping
At least one PKZ has tripped.
TYP
ERR
configuration
If the TYP
ERR
parameter is set for group diagnostics, this bit indicates an error as soon as the
ACTUAL configuration of a slave does not match the SET configuration for this position.
0
OK
The ACTUAL configuration fully matches the SET configura
-
tion or diagnostics function has been deactivated via the
parameter.
1
faulty
The actual configuration does not fully match set configu
-
ration.
U
AUXERR
Voltage
U
AUX
If the U
AUXERR
A parameter is activated,
AUXERR
will generate an error message as soon as the
power supply goes below the level at which the function of the relays is not guaranteed.
0
OK
Contactor supply voltage is o.k. (> 20 VDC) or diagnostics
function has been deactivated via this parameter.
1
under voltage
Contactor supply voltage is not o.k.
(< 18 VDC).
Design.
Value
Meaning