F29 

 
 

 

Parallel CAN Bus fault

 

1.When in parallel mode, check the parallel communication 
cableconnection and hybrid inverter communication 
address setting. 
1.During the parallel system startup period, inverters will 
report F29. 
when all inverters are in ON status, it will disappear 
automatically. 

 
 

 

F32 

 
 

 

PV to DC over current

 

1.

 

Check the PV panels charge to see if there are 

too many panels connected to one string. If the 
MPPT is overloaded, disconnect the necessary 
panels from the inverter or rebuild the connection 
of the panels to adjust the MPPT correctly. 

2.

 

Check if there is any other possibility of being 

any overcurrent to the MPPT 

F34 

AC Overcurrent fault 

1. Check the backup load connected, make sure it 
is in allowed power range. 

 

F35 

 

No AC grid

 

Please confirm grid is lost or not. 
Check the grid connection is good or not. 
Check the switch between inverter and grid is on or not. 

 

F41 

 

Parallel system stop

 

1. Check the hybrid inverter working status. If 
there's 1 pcs hybrid inverter is in OFF status, 
the other hybrid inverters may report F41

 

fault in parallel system.

 

 

 

F42 

 

 

AC line low voltage

 

1.

 

Check the AC voltage is in the range of standard 

voltage inspecification. 

2.

 

Check whether grid AC cables are firmly and 

correctlyconnected. 

 

F47 

 

AC over frequenc 

Check the frequency is in the range of specification or not. 
Check whether AC cables are firmly and correctly connected. 

 

F48 

 

AC lower frequency

 

1. 

Check the frequency is in the range of specification or not. 

2. 

Check whether AC cables are firmly and correctly connected. 

 

F56 

 

DC busbar voltage 

is too low

 

1.

 

Check whether battery voltage is too low. 

2.

 

If the battery voltage is too low, using PV or grid to 

charge thebattery. 

 

 

F58 

 

 

BMS communication fault

 

1.

 

it tells the communication between hybrid 

inverter and batteryBMS disconnected 
when"BMS_Err-Stop" is active. 

2.

 

if 

don’t

 want to see this happen, you can 

disable"BMS_Err-Stop" item on the LCD. 

F59 

AC Grid overcurrent 

1. 

Chech AC current. 

2. 

If there is no grid check the discharge battery current. 

F63 

ARC fault

 

1. 

ARC fault detection is only for US market. 

2. 

Check PV module cable connection and clear the fault. 

F64 

Heat sink high 

temperature 
failure 

1. 

Check whether the work environment temperature is too 

high. 

2. 

Turn off the inverter for 10mins and restart. 

 

 
 

9.2

 

Battery errors 

If the error appearing is related to batteries, please check the Battery Manual. 

Summary of Contents for SUNBOX 5.0 Series

Page 1: ...Instruction manual SunBox Series 5 0...

Page 2: ...lly Non compliant use use of the product in applications and or configurations not in accordance with this manual and or modifications during assembly will result in warranty cancellation and all liab...

Page 3: ...48V 5 1 kWh 15 5 7 Wheels mounting 16 5 8 Start up 16 6 Inverter Charger Configuration 17 5 4 System Setup Menu 21 5 6 Battery Setup Menu 21 5 7 System Work Mode Setup Menu 22 5 8 System work mode Me...

Page 4: ...asheet for Hybrid Inverter Hybrid Series 48V 5 0 o Instruction Manual and Datasheet for Batteries Lithium Series 48V 5 1kWh For any other questions about the inverter or the battery consult the corres...

Page 5: ...DC Four 16A fuses AC Protections A magnetothermal switch The machine has fast MC4 links that facilitate the connection of each string In terms of support and handling the system includes four wheels t...

Page 6: ...se at times when energy production is not sufficient b When the demand for electricity consumption exceeds the energy produced by photovoltaic panels the Inverter transforms the DC into AC and takes t...

Page 7: ...the system works in parallel with the grid and with photovoltaic panels Furthermore in this mode in the event of a network failure the switch automatically switches to off grid mode to continue its c...

Page 8: ...51 2V Max Charge discharge current 50A BMS communication CAN DC protections by MPPT 4 x Fuse holder and fuse 1000Vdc 15A Integrated AC protections Magnetothermic Grid Integrated Magnetothermic Load In...

Page 9: ...d from inclement weather and it is especially relevant that its location is kept dry and avoid potentially flooded areas The operating temperature range should be considered which must not exceed 50 C...

Page 10: ...eries need to be installed the SunBox Series 5 0 comes ready to store up to 2 Turbo Energy Lithium Series 48V 5 1kWh batteries Its installation is explained below The Grid and Load outputs in normal g...

Page 11: ...guration and avoids manipulation of the load connections As all the power from the network passes through the equipment Load output and it distributes the energy it implies that the maximum power of t...

Page 12: ...y despite a grid failure The rest of the loads above 11kW must be connected on the grid side In the case of not needing to connect critical loads and wanting to simplify the installation all the loads...

Page 13: ...ed For example if 3 microinverters of 1600 W are installed in series we will have a total of 4800 W 5000W If we connect 4 400W photovoltaic panels per microinverter we will have a total of 12 extra pa...

Page 14: ...the SunBox cabinet It is very important to note that each positive must be connected to its negative in the cabinet for this it is recommended to mark the cables or make connections one at a time unt...

Page 15: ...Configuration of Lithium Series Slim 48V 5 1 kWh 1 ON 0 OFF Address Dial switch position Explain 1 2 3 4 1 ON OF F OFF OF F Pack1 Master 2 OF F ON OFF OF F Pack2 3 ON ON OFF OF F Pack3 4 OF F OF F ON...

Page 16: ...e you are finished with all connections the machine is ready to start working It will proceed as follows 1 Reset the DC and AC protections at the back of the cabinet 2 Start the Batteries To do this p...

Page 17: ...r this icon F01 F64 errors detail error info can be viewed in the System Alarms menu 2 At the top of the screen is the time 3 Pressing System Setup Icon it is possible to enter in the system setup scr...

Page 18: ...power and Load power always keep positive Grid power negative means sell to grid positive means get from grid Battery power negative means charge positive means discharge 6 1 1 LCD operation flow cha...

Page 19: ...5 2 Information from Main Menu...

Page 20: ...d Solar power curve for daily monthly yearly and total can be roughly checked on the LCD For more accuracy in power generation please check on the monitoring system Click the up and down arrow to chec...

Page 21: ...em setup Beep activate desactivate alarm noise Lithium Use of the battery with communication Use Batt V Use of the battery without commmunication charge information on volts Use Batt Use of the batter...

Page 22: ...The inverter will turn on back when the battery reaches this level of charge On this screen the configuration by tension for batteries is made We can stablish the floating level absortion equalizatio...

Page 23: ...mode activated Battery does not discharge 10 00 14 00 GM mode activated The user has a lower contracted power 2500 W for this period since it is more expensive A 30 battery is reserved to supply powe...

Page 24: ...nu Generator input rated power Max power received by the inverter Configurate on 5000W as maximum In case of putting inverters in parallel divide the maximum power of the generator between the number...

Page 25: ...Fre High With this option selected when SOC is reachong the OFF value the microinverter power goes down lineally When the SOC reaches the OFF value the frequency of the system goes equal to the select...

Page 26: ...three inverters as master 2 Do not select Parallel 3 Choose a Modbus number for each one they must be different 4 Choose a diferent phase for each inverter 5 In case of including Meters select the opt...

Page 27: ...fi access password The logger creates a Wifi network whose name is AP_ followed by the serial number of the logger Step 1 Connect to the Wifi network With an electronic device with Wi Fi PC Tablet Sma...

Page 28: ...smartphone that has been connected to the logger s Wi Fi Write the text 10 10 100 254 in the address bar of the web browser A pop up window will appear to login with a username and password The defaul...

Page 29: ...the Wi Fi Step 3 1 select the Wi Fi When we run the connection wizard the list of Wi Fi networks to which the logger has access appears Among them should appear our Wi Fi We must select it and press t...

Page 30: ...d then press the Next button It is used to configure the security of the connection to the Wi Fi By selecting Hide AP the Wi Fi network will appear as a hidden network Step 3 4 If the adjustment has b...

Page 31: ...refresh the browser page Step 4 Verify the logger connection to the Wi Fi After restarting the web page log back in to the Status page and check the status of the recorder s network connection Once w...

Page 32: ...ct the DC lines one by one to verify the energy input of each panel group To do this it is mandatory to disconnect the DC disconnector prior to each disconnection of continuous lines iii Important eac...

Page 33: ...l F20 DC over current fault of the hardware 1 Check PV module connect and battery connect 2 When in the off grid mode the inverter startup with big powerload it may report F20 Please reduce the load p...

Page 34: ...ne low voltage 1 Check the AC voltage is in the range of standard voltage inspecification 2 Check whether grid AC cables are firmly and correctlyconnected F47 AC over frequenc Check the frequency is i...

Reviews: