C
om
p
on
e
nt
-N
o
el
e
m
en
t-
N
o
ac
tiv
ity
-N
o
activities
interval
components and
elements
pe
rio
d
on
d
em
a
nd
3
5
Filter for suspended matter
(Global activities can not be
appointed. They are
depending on the particular
conditions of installation and
operation)
4
Humidifier
4
1
Air washer and honeycomb
4
1
1
Check pollution, incrustation,
damaging and corrosion
Q
4
1
2
Cleaning for save function
X
4
1
3
Check function of water
supply and distribution
M
4
1
4
Check water level
M
4
1
5
Adjust regulation device for
water level
X
4
1
6
Check function of sludge
device
Q
4
1
7
Adjust sludge device
X
4
1
8
Check function of drain and
overflow
M
4
1
9
Check pollution of strainer
M
4
1
10
Clean strainer
X
4
1
11
Check function of pump
M
4
1
12
Detect bacterial count
H
4
1
13
Check hygienic condition
M
4
2
Drop eliminator / Flow straightener
4
2
1
Check pollution, incrustation,
damaging and corrosion
Q
4
2
2
Cleaning for save function
X
4
2
3
Check function of drain and
siphon
Q
4
2
4
Check hygienic condition
M
4
3
Steam humidifier with steam generator
4
3
1
Check pollution, damaging
and corrosion
Q
4
3
2
Cleaning for save function
X
4
3
3
Check function of water
supply and water level
Q
4
3
4
Check pollution of strainer
Q
4
3
5
Clean strainer
X
4
3
6
Check function of magnet
valve
M
4
3
7
Check function of ICA and
safety device
M
4
3
8
Check steam cylinder for
scaling
M
4
3
9
Change or regenerate steam
cylinder
X
4
3
10
Check function of steam
distributor and nozzles
Q
4
3
11
Check damage and tightness
of steam and condensate
hose
H
4
3
12
Check for condensate
formation
4
3
13
Check hygienic condition
M
4
4
Steam humidifier without steam generator
4
4
1
Check pollution, damaging
and corrosion
Q
4
4
2
Cleaning for save function
X
4
4
3
Check pollution of strainer
Q
4
4
4
Clean strainer
X
C
om
p
on
e
nt
-N
o
el
e
m
en
t-
N
o
ac
tiv
ity
-N
o
activities
interval
components and
elements
pe
rio
d
on
d
em
a
nd
4
4
5
Check function of regulation
valve
Q
4
4
6
Check function of steam
distributor and condensate
line
H
4
4
7
Check for condensate
formation
4
4
8
Check hygienic condition
M
4
4
9
ICA -devices see VDMA 24186 part 4
4
5
Ultrasonic- Spray- and. Hybrid humidifier
4
5
1
Check pollution, incrustation,
damaging and corrosion
Q
4
5
2
Cleaning for save function
X
4
5
3
Clean water tank
M
4
5
4
Check function of electrical
system
Q
4
5
5
Check function of energy
converter (only for ultrasonic
humidifier)
Q
4
5
6
Change energy converter
(only for ultrasonic humidifier)
X
4
5
7
Check function of water
supply and distribution
M
4
5
8
Check function of pump
Q
4
5
9
Check hygienic condition
M
5
Elements of the air distribution system
5
1
Weather lovers
5
1
1
Check pollution, damaging
and corrosion
H
5
1
2
Cleaning for save function
X
5
2
Dampers
5
2
1
Check pollution, damaging
and corrosion
H
5
2
2
Cleaning for save function
X
5
2
3
Check mechanical function
H
5
2
4
Grease bearings and
connecting rods
X
5
2
5
Damper actuator see VDMA 20186 part 4
5
3
Chambers
5
3
1
Check pollution, damaging
and corrosion
Y
5
3
2
Cleaning for save function
X
5
3
3
Check function of drain
Y
5
3
4
Clean drain
X
5
3
5
Check tightness and free
movement of doors and
hinges
Y
5
3
6
Check thermal insulation for
damaging
Y
5
3
7
Check tightness of flexible
canvas
Y
5
5
8
Clean chambers inside
X
5
5
9
Check hygienic condition
M
5
4
Fire dampers and valves
5
4
1
Check catching device for
function and damaging
Y
5
4
2
Check tripping device for
function and pollution
Y
5
4
3
Check sealing for damaging
and pollution
Y
5
4
4
Cleaning for save function
X
5
4
5
Change tripping element
X
5
4
6
Check free movement
Y
5
4
7
Check function of position
indicator
Y