Practical examples
Documentation DALI MSensor 02 | 02-2012 | en
- 32 / 38 -
Presence synchronisation for corridor with office rooms
Requirements
Switch on and switch off using motion sensor
Ambient light control of illuminance
Lighting in the corridor must remain at a basic lighting level (10%) as long as at least one office is occupied. The
lighting must only be switched off entirely when no office is occupied and there is nobody in the corridor.
Grouping/configuration:
Office A
Office B
Corridor
MSensor
Group 0
(switch position 1)
Group 1
(switch position 2)
Group 6
(switch position 7)
Configuration Reaction to presence in other groups:
Group: 0 and 1
Function: Go to Absence value
...