  Special DALI settings
Documentation DALI MSensor 02 | 02-2012 | en
- 25 / 38 -
Special DALI settings
DALI concept
The behaviour of control devices is not currently described in the DALI standard. This is why the DALI MSensor 02 responds
to some DALI commands in a special manner, as defined by Tridonic. This ensures that the DALI MSensor 02 can be
optimally combined with other products in the comfortDIM product range.
Please pay attention to notes concerning DALI commands (
) !
see chapter "Reaction to DALI commands", page 25
When used in combination with other manufacturers' controllers: please check compatibility!
The DALI MSensor 02 is designed so that it can be combined with other DALI controllers. This is why the sensor responds to
some DALI commands in a different way than that specified in the official DALI standard. This ensures that other DALI
controllers, e.g. the DALI SC or x-touchPanel, can be used to affect light control.
Like DALI control gear, the DALI MSensor 02 reacts to commands that are sent to it, i.e. commands sent to its DALI address,
DALI group (luminaire group), or to broadcast commands.
Reaction to DALI commands
The DALI MSensor 02 sometimes distinguishes whether commands are sent to its DALI address or to its DALI group or
whether commands are broadcast commands. This chapter deals with the most important commands for communicating with
other controllers and confines itself to broadcast or group commands. A detailed overview of supported DALI commands sent
to a DALI address can be found in the annex (
).
see chapter "Commands to DALI address", page 37
Direct setpoint invocation (DALI "Direct Arc Power x" command)
In the case of direct setpoint invocation, a distinction must be made between setpoint commands greater than 0% and
setpoint commands equal to 0%. Setpoint commands greater than 0% act as a switch-on command. The following behaviour
applies for these:
Constant light control:
Setpoint is invoked, light control is temporarily disabled.