Constant light control
Documentation DALI MSensor 02 | 02-2012 | en
- 13 / 38 -
The diameter of the detection area depends on the detection angle of the sensor and the height at which it is mounted.
Calculating the diameter:
d1 = 2 × tan(0.5 × 70°) × h
Typical example values of detection area:
Height h Ø d1
2.0 m
2.8 m
2.5 m
3.5 m
3.0 m
4.2 m
3.5 m
4.9 m
4.0 m
5.6 m
Operating modes
The ambient light sensor has three operating modes. Constant light control can be activated or deactivated. Constant light
control can also be deactivated temporarily.
Ambient light
control:
"enabled"
Light control of the luminaire group is activated by triggering the DALI MSensor 02.
Ambient light
control:
"disabled"
The light control of the DALI MSensor 02 is permanently deactivated. A fixed setpoint in the luminaire
group is invoked by triggering the DALI MSensor 02.