Tridonic DALI MSensor 02 Product Manual Download Page 1

luxCONTROL

Product manual DALI MSensor 02

Summary of Contents for DALI MSensor 02

Page 1: ...luxCONTROL Product manual DALI MSensor 02 ...

Page 2: ......

Page 3: ...ing and settings 10 Functions 12 Constant light control 12 Presence control 17 Remote control 21 Special DALI settings 25 Enhanced functionality 29 Practical examples 30 Individual office rooms 30 Corridor 31 Neighbourhood function 32 Disposal 33 Compliance 34 Reference list 35 Appendix 36 Commands for broadcast and luminaire groups 36 Commands to DALI address 37 ...

Page 4: ...ll result in incorrect operation Please make sure you are using an up to date version of the masterCONFIGURATOR software TRIDONIC GmbH Co KG is constantly striving to develop all its products This means that there may be changes in form equipment and technology Claims cannot therefore be made on the basis of information diagrams or descriptions in these instructions The latest version of these ope...

Page 5: ... use could result in injury malfunction or damage to property The operator must inform all usersof the potential risks associated with the use of the equipment and of protective countermeasures Dangers associated with the operation of the system Danger Danger of electrocution Disconnect the power to the entire lighting system before working on the lighting system Caution Risk of damage caused by c...

Page 6: ...ble to activate light control by the DALI MSensor 02 by calling up a scene see chapter Special DALI settings page 25 Presence synchronisation with other DALI MSensor 02 groups The DALI MSensor 02 makes it possible to set up presence synchronsiation between several DALI MSensor 02 groups In doing so it is possible to specify how the DALI MSensor 02 should respond to any presence in other groups see...

Page 7: ...sensor controls a DALI group directly Besides Direct master mode the DALI MSensor 02 also supports two further modes for use in combination with a higher level DALI master controller Indirect master mode Slave mode The following chapters deal with Direct master mode in detail Later on the see chapter Enhanced functionality page 29 other two modes are dealt with briefly ...

Page 8: ...ing Surface mounted Box mounted The DALI MSensor 02 is designed for the following principal applications Individual offices Open plan offices Training presentation rooms Corridors passageways and garages The DALI MSensor 02 either controls all the units on the DALI circuit or a DALI group The DALI MSensor 02 is Multi master compatible i e it can be used in conjunction with other DALI controllers i...

Page 9: ...re its own power supply It can be connected to the DALI circuit without bothering about polarity Power is supplied via the DALI circuit The sensor draws 6 mA Notice A maximum of 12 DALI MSensors 02 can be operated on a single DALI circuit If more sensors are connected the increased data traffic this causes has an adverse affect on the light control function ...

Page 10: ...roup Otherwise the sensors will not interpret commands sent to the luminaire correctly Unlike other DALI controllers a DALI address is assigned to the DALI MSensor 02 during addressing This reduces the total number of available DALI addresses This must be taken into account when designing the DALI circuit Extending an existing DALI circuit The DALI MSensor 02 can be used in an existing DALI circui...

Page 11: ...or V1 5 or earlier It is only possible to replace a faulty DALI MSensor V1 5 or earlier by a DALI MSensor 02 if specific preconditions are met Make sure that there is no other DALI MSensor V1 5 or earlier in the DALI group in question Make sure that the faulty DALI MSensor V1 5 or earlier is not influenced by other DALI controllers e g by the fact that a DALI GC activates daylight based control vi...

Page 12: ...oint at every sensor Where ambient light values are high this can result in ambient light based bright out and bright in If the measured illuminance exceeds a specified threshold value for a period of time that is longer than the specified delay time the luminaire group is switched off by the DALI MSensor 02 This also applies in cases where motion is detected in the room The luminaire group is swi...

Page 13: ...m 3 0 m 4 2 m 3 5 m 4 9 m 4 0 m 5 6 m Operating modes The ambient light sensor has three operating modes Constant light control can be activated or deactivated Constant light control can also be deactivated temporarily Ambient light control enabled Light control of the luminaire group is activated by triggering the DALI MSensor 02 Ambient light control disabled The light control of the DALI MSenso...

Page 14: ...ase of incorrect operation or unsatisfactory results adjust the brightness setpoint Notice A suitable brightness setpoint is typically defined by using a lux meter to make a localised brightness measurement The results obtained may vary depending where the measurement is made and what the external lighting conditions are Check ambient light control at various locations within the measuring area an...

Page 15: ...aylight This light must be detected correctly and completely Prevent measurements being falsified by other light sources Positioning the ambient light sensor correctly is crucial 1 In order to be able to control ambient lighting properly the sensor must be able to detect the light from the controlled luminaires completely Position the sensor so that the sensor s detection area lies within the area...

Page 16: ...r enough away from any window area Make sure that any glare or sunlight reflected by shiny glass or metal surfaces cannot hit the sensor 3 If more than one sensor is being used in a room it is possible that the detection areas of the sensors may overlap Overlapping detection areas may cause the different control circuits to affect one another and this may lead to false results Position the sensors...

Page 17: ...r heat sources e g photocopiers radiators etc may have an adverse affect on presence based control Make sure that there are no other heat sources in the immediate vicinity of the sensor Detection area of the motion sensor The detection area of the motion sensor consists of a pattern of various measurement fields The following conditions must be met in order for an object to be detected reliably Th...

Page 18: ... by display screens backs etc Operating modes The motion sensor has four different operating modes Operating mode enabled The light is switched on or off automatically in response to the presence of a person Operating mode enabled only OFF The sensor switches off if there is no motion detected in the detection area but does not switch on again even if motion is detected Switch on must be obtained ...

Page 19: ...ead time manual OFF parameter If the sensor detects motion during the time lag it restarts the time lag afresh The motion sensor is reactivated when the time lag has elapsed Commissioning Setting the operating mode The individual operating modes can be set in the masterCONFIGURATOR software V2 02 or later see chapter Source directory page 35 Setting the profile The individual profiles can be set i...

Page 20: ...to the absence value If the sensor is at the absence value the synchronisation command is ignored MASK The DALI MSensor 02 ignores the Motion detected synchronisation command of the other group factory setting Notice In the operating mode enabled only OFF the DALI MSensor 02 does not send synchronisation commands until the sensor has been activated by a manual switch on command In the operating mo...

Page 21: ... to operate the assigned luminaire group in the DALI system This remote control offers the following functions Switching luminaire group on off Dimming luminaire group up down Activation of light control Definition of the brightness setpoint value A IR sender E OFF Luminaire group OFF B AUTOMATIC control mode ON OFF F UP Increase light value C SET Saves the current light control value G DOWN Reduc...

Page 22: ...e that the remote control can be used straight away without any complicated set up procedure the buttons are pre programmed with a default setting The button assignment in User mode is as follows A IR sender B LED status display I Switch all luminaires in the DALI system ON or OFF C Light value 100 brightness J Increase or reduce the light value dimming the DALI system D Light value 50 brightness ...

Page 23: ...naire group that is set on the DALI MSensor 02 This setting is made via the DALI MSensor 02 see chapter Commissioning and settings page 10 DALI RC The rotary switch in the battery compartment of the remote control is used for setting the group to be controlled by the remote control Position 0 means that the commands apply to all the control gear Positions 1 15 mean that the commands apply only to ...

Page 24: ...2 1 3 9 2 8 A F 9 14 Notice If the masterCONFIGURATOR software is used to customise the button assignments the rotary switch in the battery compartment of the remote control is disabled The commands will then only apply to the luminaire group selected on the DALI MSensor 02 ...

Page 25: ...r x touchPanel can be used to affect light control Like DALI control gear the DALI MSensor 02 reacts to commands that are sent to it i e commands sent to its DALI address DALI group luminaire group or to broadcast commands Reaction to DALI commands The DALI MSensor 02 sometimes distinguishes whether commands are sent to its DALI address or to its DALI group or whether commands are broadcast comman...

Page 26: ... Switch on at maximum value DALI Recall Max command Constant light control This behaviour can be adjusted in the masterCONFIGURATOR configuration software The maximum value of the control gear is invoked light control is temporarily disabled or The maximum value of the control gear is invoked light control is activated Presence control In switched off state presence detector is activated and chang...

Page 27: ...he masterCONFIGURATOR configuration software Luminaire group is dimmed light control is temporarily deactivated or Luminaire group is dimmed The brightness value measured after dimming is accepted as the new temporary brightness setpoint for constant light control At the next switch on constant light control is reset to the previously stored brightness setpoint Presence control In switched off sta...

Page 28: ...NEL controllers the DALI commands that are used can be modified in the masterCONFIGURATOR software The particular DALI command that is invoked then depends on the settings Scene recalls using the DALI SC DALI TOUCHPANEL factory setting x touchBOX or x touchPANEL are sent to all devices this means that all DALI MSensors 02 with appropriate parametrisation respond to them ...

Page 29: ...it sends the measured light value presence detection status and remote control status to a higher level master The master controller analyses this information and sends the corresponding control commands to the luminaires eDALI is used to communicate with the master eDALI is Tridonic GmbH Co KG s proprietary extension of the DALI standard Slave mode In Slave mode the DALI MSensor 02 do not send an...

Page 30: ...DALI MC is used to switch on light control and to switch off the lighting Activation of light control with scene recall Switch off with OFF Configuration of input 1 Target Group 0 Function Momentary action switch Command X Recall scene 0 Configuration of input 2 Target Group 0 Function Momentary action switch Command X OFF The DALI MC is used to switch on light control and to switch off the lighti...

Page 31: ... Corridor Staircase MSensor Group 0 switch position 1 Group 1 switch position 2 Notice In order to enlarge the presence detection area several DALI MSensors 02 are installed in the corridor All these sensors must be assigned to the same luminaire group If there are multiple DALI MSensors 02 in a group light control behaves as follows the light value is raised until it is no longer less than the se...

Page 32: ...the corridor must remain at a basic lighting level 10 as long as at least one office is occupied The lighting must only be switched off entirely when no office is occupied and there is nobody in the corridor Grouping configuration Office A Office B Corridor MSensor Group 0 switch position 1 Group 1 switch position 2 Group 6 switch position 7 Configuration Reaction to presence in other groups Group...

Page 33: ...02 2012 en 33 38 Disposal For disposal in accordance with the WEEE Directive Return the device to Tridonic or dispose of the device in accordance with national regulations Do not dispose of the device in nonrecyclable waste Do not burn the device ...

Page 34: ... interference all the EMC requirements are met also for the luminaire Radio interference is heavily dependent on the design of the luminaire and the wiring so it has to be measured in conjunction with the luminaire The limit values for EMC are given in the following standards EN 55015 Limit values and measuring procedures for radio interference EN 61547 EMC requirements With the CE symbol on its p...

Page 35: ...idonic com com en download certificates ENEC_IK 1965_DALI_MSensor pdf Downloads Tridonic software http www tridonic com com en software asp Download masterCONFIGURATOR http www tridonic com com en software masterconfigurator asp Additional information DALI manual http www tridonic com com en download technical DALI manual_en pdf Guarantee conditions http www tridonic com com en guarantee asp Data ...

Page 36: ... light level Lighting control is temporarily disabled static operation Dimming light level Lighting control is temporarily disabled static operation STEP DOWN AND OFF Dimming light level Lighting control is temporarily disabled static operation Dimming light level Lighting control is temporarily disabled static operation RECALL MIN LEVEL MIN LEVEL is called up Lighting control is temporarily disab...

Page 37: ...E DTR 96 111 ADD TO GROUP 112 127 REMOVE FROM GROUP 128 STORE DTR AS SHORT ADDRESS 144 QUERY STATUS Response is always b00010000 145 QUERY BALLAST 149 QUERY RESET STATE 150 QUERY MISSING SHORT ADDRESS 151 QUERY VERSION NUMBER 152 QUERY CONTENT DTR 153 QUERY DEVICE TYPE Response is b11111110 160 QUERY ACTUAL LEVEL Query brightness value and status of motion sensor 192 QUERY GROUPS 0 7 193 QUERY GRO...

Page 38: ... status LLL LLLL bits 6 0 Brightness 1 Motion detected 0 No motion detected Binary coded brightness Brightness code LLL LLLL bits 0 6 Binary representation of brightness in lx Brightness values in lx 11xxxxx 1xxxxx0000 512 1008 lx in 16 lx increments 10xxxxx 01xxxxx000 256 504 lx in 8 lx increments 01xxxxx 001xxxxx00 128 252 lx in 4 lx increments 00xxxxx 000xxxxx00 0 124 lx in 4 lx increments Noti...