![Triconex Trident Planning And Installation Manual Download Page 66](http://html.mh-extra.com/html/triconex/trident/trident_planning-and-installation-manual_1162141066.webp)
50
Input/Output Modules
Trident Planning and Installation Guide
Common Specifications
Wiring Terminals
Logic Power
Feature
Specification
Compression terminals
Compatible with 24 to 12 (0.2 mm
2
to 3.3 mm
2
)
AWG wiring
Feature
Specification
Nominal input voltage
24 V DC
Voltage range
24 V DC –15% or +20% + 5% AC ripple
(19.2 to 30 V DC)
Logic power
<3 W
Absolute maximum input voltage
33 V DC
Absolute maximum reverse input
voltage
–0.6 V DC
Input power interruption time
from nominal
1 ms maximum
Power interruption interval
1 sec minimum
Reverse current isolation input to
input
500
µ
A maximum
Inrush current per input
2.4 A maximum
Short circuit current limit per input
2.4 A maximum
Functional-earth-to-logic-ground
isolation
0 V, no isolation
Protective-to-functional-earth
isolation
500 V DC, minimum
Summary of Contents for Trident
Page 1: ...Trident Version 1 2 Triconex An Invensys Company Planning and Installation Guide ...
Page 10: ...x Contents Trident Planning and Installation Guide ...
Page 16: ...xvi Training Trident Planning and Installation Guide ...
Page 53: ...Main Processor Module 37 Chapter 3 System Description Model 2101 Main Processor Baseplate ...
Page 140: ...124 Covers Trident Planning and Installation Guide ...
Page 216: ...200 Replacing Modules Trident Planning and Installation Guide ...
Page 238: ...222 Diagread Cables and Debug Connectors Trident Planning and Installation Guide ...
Page 240: ...224 Trident Planning and Installation Guide ...
Page 248: ...232 Trident Planning and Installation Guide ...
Page 264: ...248 Glossary Trident Planning and Installation Guide ...
Page 274: ...258 Index Trident Planning and Installation Guide ...