Guidelines
127
Chapter 4
Installation and Maintenance
The following table represents possible configurations.
Maximum Points
The following table lists the maximum number of points you can use for each type
of I
⁄
O module. You can install any combination of module types within the limit of
each point type.
Mechanical Installation
This section provides general guidelines for mounting a panel for controller
components.
!
WARNING
In hazardous locations, a Trident controller must be mounted in a cabinet or rack
with a sealed bottom.
AO
Modules
PI
Modules
All Other I/O
Modules
0
0
14
1
0
9
0
1
9
2
0
8
2
1
7
Module Type
Maximum Points
Analog Input Module
448
Analog Output Module
8
Digital Input Module
448
Digital Output Module
224
Pulse Input Module
6
Solid-State Relay Output Module
448
Summary of Contents for Trident
Page 1: ...Trident Version 1 2 Triconex An Invensys Company Planning and Installation Guide ...
Page 10: ...x Contents Trident Planning and Installation Guide ...
Page 16: ...xvi Training Trident Planning and Installation Guide ...
Page 53: ...Main Processor Module 37 Chapter 3 System Description Model 2101 Main Processor Baseplate ...
Page 140: ...124 Covers Trident Planning and Installation Guide ...
Page 216: ...200 Replacing Modules Trident Planning and Installation Guide ...
Page 238: ...222 Diagread Cables and Debug Connectors Trident Planning and Installation Guide ...
Page 240: ...224 Trident Planning and Installation Guide ...
Page 248: ...232 Trident Planning and Installation Guide ...
Page 264: ...248 Glossary Trident Planning and Installation Guide ...
Page 274: ...258 Index Trident Planning and Installation Guide ...