Analog Output Module Indicators
Trident Planning and Installation Guide
AO Field Alarm Indicator
The AO field fault indicator is lit when a field power problem has occurred.
Field
Alarm
Description
Action
Yellow
steady
Field power from one or more
of the redundant sources is
missing or a field error is
detected. A field error may be
an open load or an out-of-
compliance error.
To isolate the missing power source, use
the TriStation Diagnostic Panel.
To determine the actual state, use a
voltmeter, then correct the problem in the
external circuit.
If these steps do not solve the problem,
replace the module.
Summary of Contents for Trident
Page 1: ...Trident Version 1 2 Triconex An Invensys Company Planning and Installation Guide ...
Page 10: ...x Contents Trident Planning and Installation Guide ...
Page 16: ...xvi Training Trident Planning and Installation Guide ...
Page 53: ...Main Processor Module 37 Chapter 3 System Description Model 2101 Main Processor Baseplate ...
Page 140: ...124 Covers Trident Planning and Installation Guide ...
Page 216: ...200 Replacing Modules Trident Planning and Installation Guide ...
Page 238: ...222 Diagread Cables and Debug Connectors Trident Planning and Installation Guide ...
Page 240: ...224 Trident Planning and Installation Guide ...
Page 248: ...232 Trident Planning and Installation Guide ...
Page 264: ...248 Glossary Trident Planning and Installation Guide ...
Page 274: ...258 Index Trident Planning and Installation Guide ...