Effective Grounding Methods
153
Chapter 4
Installation and Maintenance
Notes
L
should be connected to
at one and only one place for each set of
redundant field power supplies. Multiple I
⁄
O modules can share a single set of
power supplies. Or, each I
⁄
O module or group of modules can use separate power
supplies referenced to alternate grounds. Alternatively, L
can be connected to
a DCS master reference ground or other quiet earth. In simple environments, logic
and field power can be combined and treated as one ground system.
Grounding Field
Power
J5
1
2
1
Typical I/O
Baseplate
Power
Disconnect
Power
Disconnect
Distribution
Block
F
Power
Supply 1
Power
Supply 2
–
–
+
+
1
2
3
1
2
Extender
Summary of Contents for Trident