188
Digital Output Module Indicators
Trident Planning and Installation Guide
DO Power/Load Indicator
The DO power/load indicator is lit when a power/load problem has occurred.
DO Point Indicator
The DO point indicators identify whether the point is energized or not energized.
Power/
Load
Description
Action
Yellow
steady
For at least one point, the
commanded state and the
measured state do not agree.
To isolate the suspected point, use the
TriStation Diagnostic Panel.
To determine the commanded state of the
output point, use the TriStation
Control
Panel.
To determine the actual state of the
output, use a voltmeter, then correct the
problem in the external circuit.
Verify that load current is within product
specification.
If these steps do not solve the problem,
replace the module.
Point (1-16)
Description
Green steady
Field circuit is energized.
No light
Field circuit is not energized.
Summary of Contents for Trident
Page 1: ...Trident Version 1 2 Triconex An Invensys Company Planning and Installation Guide ...
Page 10: ...x Contents Trident Planning and Installation Guide ...
Page 16: ...xvi Training Trident Planning and Installation Guide ...
Page 53: ...Main Processor Module 37 Chapter 3 System Description Model 2101 Main Processor Baseplate ...
Page 140: ...124 Covers Trident Planning and Installation Guide ...
Page 216: ...200 Replacing Modules Trident Planning and Installation Guide ...
Page 238: ...222 Diagread Cables and Debug Connectors Trident Planning and Installation Guide ...
Page 240: ...224 Trident Planning and Installation Guide ...
Page 248: ...232 Trident Planning and Installation Guide ...
Page 264: ...248 Glossary Trident Planning and Installation Guide ...
Page 274: ...258 Index Trident Planning and Installation Guide ...