226
General Considerations
Trident Planning and Installation Guide
General Considerations
The following general considerations should be observed when installing the
Trident system:
• Maintain an ambient air temperature of 60°C (140°F) or less at the bottom
of each baseplate.
• Separate all 440 V AC (or higher) electrical supply lines as far away from
the components as possible.
• Separate AC and data wiring as much as possible.
• Use best industry practices when installing wiring. For more information,
see
IEEE Standard 518-1977.
• Do not run cables parallel if they carry different types of signals (data versus
power); instead, cross the cables at right angles.
• Maintain shield continuity and verify that shield leads are not broken.
• Route cables around, rather than through, high noise areas.
• Route shielded data cable along grounded surfaces such as metal cabinet
walls and in conduit or trays. Single-shielded cable is most effective when
routed along grounded surfaces.
• Allow the minimum amount of unshielded wire that will accommodate the
connection.
Summary of Contents for Trident
Page 1: ...Trident Version 1 2 Triconex An Invensys Company Planning and Installation Guide ...
Page 10: ...x Contents Trident Planning and Installation Guide ...
Page 16: ...xvi Training Trident Planning and Installation Guide ...
Page 53: ...Main Processor Module 37 Chapter 3 System Description Model 2101 Main Processor Baseplate ...
Page 140: ...124 Covers Trident Planning and Installation Guide ...
Page 216: ...200 Replacing Modules Trident Planning and Installation Guide ...
Page 238: ...222 Diagread Cables and Debug Connectors Trident Planning and Installation Guide ...
Page 240: ...224 Trident Planning and Installation Guide ...
Page 248: ...232 Trident Planning and Installation Guide ...
Page 264: ...248 Glossary Trident Planning and Installation Guide ...
Page 274: ...258 Index Trident Planning and Installation Guide ...