142
Guidelines
Trident Planning and Installation Guide
Alarm Wiring
Alarms are asserted when the controller detects a system alarm or a program alarm.
Each MP Module supports the following redundant alarm contacts:
Set 1
• Normally closed (NC) contact
• Common (C)
Set 2
• Normally closed (NC) contact
• Common (C)
A control engineer should specify the actual use of these contacts. Typically, alarm
wiring is connected to a local or remote annunciator. These devices can be wired
in parallel with the alarm wiring so that the designated alarm goes off when either
contact signals an alarm condition. For more information on program alarms, see
the
TriStation 1131 Developer's Guide.
Alarm Connections
Alarm 1/NC
A
2/NC
larm
A
1/C
larm
A
2/C
larm
MP A
MP B
MP C
MP Baseplate
Summary of Contents for Trident
Page 1: ...Trident Version 1 2 Triconex An Invensys Company Planning and Installation Guide ...
Page 10: ...x Contents Trident Planning and Installation Guide ...
Page 16: ...xvi Training Trident Planning and Installation Guide ...
Page 53: ...Main Processor Module 37 Chapter 3 System Description Model 2101 Main Processor Baseplate ...
Page 140: ...124 Covers Trident Planning and Installation Guide ...
Page 216: ...200 Replacing Modules Trident Planning and Installation Guide ...
Page 238: ...222 Diagread Cables and Debug Connectors Trident Planning and Installation Guide ...
Page 240: ...224 Trident Planning and Installation Guide ...
Page 248: ...232 Trident Planning and Installation Guide ...
Page 264: ...248 Glossary Trident Planning and Installation Guide ...
Page 274: ...258 Index Trident Planning and Installation Guide ...