I
⁄
O Extender Modules
115
Chapter 3
System Description
I
⁄
O Extender Modules
The following I
⁄
O Extender Modules Kits are available.
The purpose of an I
⁄
O Extender Module is to:
• Extend the TMR I
⁄
O bus from one I
⁄
O column to another I
⁄
O column
• Provide TMR I
⁄
O bus termination
• Provide additional input terminals for I
⁄
O module logic power
• Provide a protective earth (safety ground) connection
An I
⁄
O Extender Module contains:
• Three DB-9-pin I
⁄
O bus connectors, one per channel
• Two 24-volt logic power input terminal blocks, each with fuse and blown-
fuse indicators
• One protective earth terminal block
A maximum of eight baseplates may be stacked end-to-end in a column. To extend
a system beyond eight baseplates or to separate the baseplates so that they are not
connected end-to-end, a pair of I
⁄
O Extender Modules should be used.
Model
Description
2281
I
⁄
O Extender Module Kit (without termination)
2291
I
⁄
O Extender Module Kit for I
⁄
O Baseplate (with termination)
2292
I
⁄
O Extender Module Kit for MP Baseplate (with termination)
Summary of Contents for Trident
Page 1: ...Trident Version 1 2 Triconex An Invensys Company Planning and Installation Guide ...
Page 10: ...x Contents Trident Planning and Installation Guide ...
Page 16: ...xvi Training Trident Planning and Installation Guide ...
Page 53: ...Main Processor Module 37 Chapter 3 System Description Model 2101 Main Processor Baseplate ...
Page 140: ...124 Covers Trident Planning and Installation Guide ...
Page 216: ...200 Replacing Modules Trident Planning and Installation Guide ...
Page 238: ...222 Diagread Cables and Debug Connectors Trident Planning and Installation Guide ...
Page 240: ...224 Trident Planning and Installation Guide ...
Page 248: ...232 Trident Planning and Installation Guide ...
Page 264: ...248 Glossary Trident Planning and Installation Guide ...
Page 274: ...258 Index Trident Planning and Installation Guide ...