APPLICATION HINTS FOR THE AUXILIARY TERMINALS
The tamper switch is Normally Closed while the keypad
is secured on gang box. It is open when the keypad
is removed from the gang box. To prevent sabotage,
connect these terminals in series with a 24 hour N.C.
protection zone of an alarm system if required.
(A) TAMPER N.C.
40
With the help of a Normally Closed door
position sensor (usually a magnetic door
switch) on the door to set up the following
functions:
Door Auto Relock
-- The system will immediately
relock the door after a valid access has been gained to
prevent "tailgate" entries.
Door Forced-open Alarm
-- The keypad will generate
alarm instantly if the door is forced to open. Enable the
function at Location 80.
Door Propped-up Alarm
-- The keypad will generate
alarm if the door is left open longer than the pre-set
delay time. Enable the function at Location 81.
Inter-lock Control
-- When the door is open, the
interlock output of the keypad will give a (-) command
to stop the other keypad in an inter-lock system.
Door Opening Alarm
-- Door Opening Alarm is
designed for the emergency door only. It is always
given when the door is opened unless a valid user
code or card is used prior to the door is opened. Enable
the function at Location 91.
a)
b)
c)
d)
e)
(B) DOOR SENS
The Alarm Output switches to (-) ground in door forced to open or the door open after Egress Delay. You may
use it to turn ON an LED lamp and/ or a small buzzer to notify a guard; or connect it to a 24 hour Normally
Open protection zone of an alarm system. See Location 80 and Location 91 for more information about these
functions.
Only one connection option is recommended. Make sure that the sink current does not exceed the maximum
rating of 100mA.
(C) ALARM OUTPUT -- SET THE "K OR A" JUMPER TO "A"