EXAMPLES:
Example 1:
Set Egress Button in Momentary contact 5 seconds with delay & warning beep
90
2
5
#
(a) (b) (c) (d)
(a)
Egress function programming,
(b)
Momentary contact with warning,
(c)
Delay time of 5 seconds to release door,
(d)
Entry confirmation
Example 2:
Set Egress Button in Holding contact of 10 seconds with warning beep
90
5
10
#
(a) (b) (c) (d)
(a)
Egress function programming,
(b)
Holding contact mode with warning,
(c)
Holding time of 10 seconds to release
door,
(d)
Entry confirmation
Example 3:
Set Egress Button in Momentary contact without delay (This is the default setting)
90
1
0
#
(a) (b) (c) (d)
(a)
Egress function programming,
(b)
Momentary contact without delay,
(c)
Release door instantly,
(d)
Entry
confirmation
DOOR OPENING ALARM & TIMER (Location 91)
ALARM & TIMING OF DOOR OPENING
0
--- No Alarm – (Default)
The Alarm Output is disabled
1
–
999
--- Alarm Timer
The Door Open Alarm operates the Alarm Output (Terminal 13) only. It is mainly prepared to trigger an optional
alarm system. Put any Timing Figure of 1 to 999 into the box to enable the function of the Door Opening Alarm.
The figure is the time in second of the alarm duration, which starts to count after the door is opened and it resets
automatically when the time reaches.
The alarm can be stopped with the User Codes/Cards or the Super User PIN for Output 1 at any time before the end
of the alarm time.
NOTE:
The Door Opening Alarm is designed to protect the emergency exit door from use by the un-authorized person.
The alarm occurs when the door is opened or forced to open. However, Alarm will not happen if the door is opened
with a valid User Code or Card.
The Manner of The Door Opening Alarm:
a) The door is forced to open without using PIN/Card –
Alarm
b) The door is opened with Egress Button –
Alarm
c) The door is opened with PIN/Card –
No Alarm
To prevent confusion of the alarm outputs. It is suggested to disable the "Door Forced Open Warning" at Location 80
while "Door Opening Alarm" function is enabled. If both functions at Location 80 and Location 91 are enabled and are
set with different timings, the system will combine them and will take the longer one for alarm time.
CLOSE THE PROGRAMMING MODE (
* *
)
Always close programming mode with
* *
to set system back to normal Operation after programming.
The button is equivalent to the
*
button in the keypad with bell button.
VALIDATION
**
------------------------------- System is back to normal operation mode
ALARM TIME
VALIDATION
LOCATION
0
or
1
-
999
91
#
.