System Start-Up
Compressor Start-Up
1. Ensure that the main power disconnect switch and the control power cir-
cuit breaker for the “System Solution Pump” is “On”.
2. Before closing the main power disconnect switch for the unit, ensure that
the compressor discharge service valve and the liquid line service valve
for each circuit is back seated.
CAUTION
Compressor Damage!
Compressor service valves must be fully opened before start-up
(suction, discharge, liquid line, and oil line). Failure to fully open valves
prior to start-up may cause compressor failure due to lack of refrigerant
and/or oil flow.
3. Remove the protective plastic coverings that shipped over the compres-
sors.
4. Check the compressor oil levels. The oil level in each manifolded set of
compressor sight glasses should be equally 1/2 to 3/4 full when they are
“Off”.
5. Check the condenser coils. They should be clean and the fins should be
straight. Straighten any bent coil fins with an appropriate sized fin comb.
6. Turn the main power disconnect switch or circuit protector switch that
provides the supply power to the unit’s terminal block 1TB1 or the unit
mounted disconnect switch 1S14 to the “On” position.
7. Turn the 24 volt control circuit switch 1S70 to the “On” position.
8. Open the Human Interface access door, located in the unit control panel,
and press the SERVICE MODE key to display the first service screen.
Refer to the latest edition of the CGAF-PTG for the SERVICE TEST
screens and programming instructions.
9. Use Table 10 to program the following system components for operation
by scrolling through the displays;
20 through 30 Ton
40 through 60 Ton
Compressor 1A (On)
Compressor 1A (On)
Compressor 1B (Off)
Compressor 1B (Off)
Condenser Fans (On)
Compressor 2A (Off)
Solution Pump (On)
Compressor 2B (Off)
Condenser Fans (On)
Solution Pump (On)
Summary of Contents for CSRA025FAF0
Page 6: ...6 CSRA SVX02A EN General Information Figure 1a Model Number Description...
Page 18: ...18 CSRA SVX02A EN Installation Figure 4a C25 Ton Unit Dimensional Data Recommended Clearances...
Page 19: ...CSRA SVX02A EN 19 Installation Figure 4b C40 Ton Unit Dimensional Data Recommended Clearances...
Page 20: ...20 CSRA SVX02A EN Installation Figure 4c C60 Ton Unit Dimensional Data Recommended Clearances...
Page 47: ...CSRA SVX02A EN 47 Installation Figure 20A Typical Field Control Connections Diagram...
Page 48: ...48 CSRA SVX02A EN Installation Figure 20B Typical GBAS 0 5 Volt Connections Diagram...
Page 49: ...CSRA SVX02A EN 49 Installation Field Connection Diagram Notes for all System Control Options...
Page 65: ...CSRA SVX02A EN 65 System Start Up Figure 22 Condenser Fan Locations...