Installation
Dixon Coupling
• The Dixon coupling (See Figure 7), bolts are to be torqued prior to
charging the hose with water to 40 ft-lbs. DO NOT EXCEED 40 ft-lbs.
(The torque must be applied evenly between the bolts to ensure a
consistent gap on each side of the coupling. Some pinching of the
excess hose in the gap area is considered normal and will not create
a leak or premature failure.)
• Continually monitor and retighten, if necessary, on monthly inspec-
tion intervals.
Figure 7 — Dixon Coupling
The following figures illustrate the correct and incorrect methods for
installing hose in a horizontal hookup application.
Figure 8 — Correct Horizontal Hose Installation
Correct horizontal hose installation shows a correct hose installation. In this
configuration either a 45° or 90° elbow can be installed. This elbow prevents
stretching and crimping of the hose at the hose coupling connection. This
elbow also directs the hose to the ground at an appropriate angle to
minimize the crimping of the hose at the ground or supporting surfaces.
Summary of Contents for CSRA025FAF0
Page 6: ...6 CSRA SVX02A EN General Information Figure 1a Model Number Description...
Page 18: ...18 CSRA SVX02A EN Installation Figure 4a C25 Ton Unit Dimensional Data Recommended Clearances...
Page 19: ...CSRA SVX02A EN 19 Installation Figure 4b C40 Ton Unit Dimensional Data Recommended Clearances...
Page 20: ...20 CSRA SVX02A EN Installation Figure 4c C60 Ton Unit Dimensional Data Recommended Clearances...
Page 47: ...CSRA SVX02A EN 47 Installation Figure 20A Typical Field Control Connections Diagram...
Page 48: ...48 CSRA SVX02A EN Installation Figure 20B Typical GBAS 0 5 Volt Connections Diagram...
Page 49: ...CSRA SVX02A EN 49 Installation Field Connection Diagram Notes for all System Control Options...
Page 65: ...CSRA SVX02A EN 65 System Start Up Figure 22 Condenser Fan Locations...