Installation
Table 6 — DC Conductors
Controls using DC Communication Links
Before installing any connecting wiring between the unit and components
utilizing a DC communication link, refer to the connection diagram that
shipped with the unit for the electrical access and connection locations
provided on the unit.
A. Wiring for the components utilizing a DC communication link must be
shielded cable (Belden 8760 or equivalent). Ground the shield at one end
only.
B. Table 6 lists the conductor sizing guidelines that must be followed when in-
terconnecting a communication link to the unit.
C. Communication link must not exceed 5,000 feet maximum for each link.
D. Communication link must not pass between buildings.
E. Do not run the electrical wires transporting DC signals in or around conduit
housing AC voltage wires.
Table 7 — Maximum Communications Wiring Length
PF/FT = Picofarads/foot
Distance from
Unit to Control
Recommended
Wire Size
000 - 499 feet
16 gauge
500 - 1000 feet
14 gauge
Maximum
Communication
Link Wiring Length
Maximum
Capacitance
Between
Conductors
1,000 feet
Up to 60 PF/FT
2,000 feet
Up to 50 PF/FT
3,000 feet
Up to 40 PF/FT
4,000 feet
Up to 30 PF/FT
5,000 feet
Up to 25 PF/FT
Summary of Contents for CSRA025FAF0
Page 6: ...6 CSRA SVX02A EN General Information Figure 1a Model Number Description...
Page 18: ...18 CSRA SVX02A EN Installation Figure 4a C25 Ton Unit Dimensional Data Recommended Clearances...
Page 19: ...CSRA SVX02A EN 19 Installation Figure 4b C40 Ton Unit Dimensional Data Recommended Clearances...
Page 20: ...20 CSRA SVX02A EN Installation Figure 4c C60 Ton Unit Dimensional Data Recommended Clearances...
Page 47: ...CSRA SVX02A EN 47 Installation Figure 20A Typical Field Control Connections Diagram...
Page 48: ...48 CSRA SVX02A EN Installation Figure 20B Typical GBAS 0 5 Volt Connections Diagram...
Page 49: ...CSRA SVX02A EN 49 Installation Field Connection Diagram Notes for all System Control Options...
Page 65: ...CSRA SVX02A EN 65 System Start Up Figure 22 Condenser Fan Locations...