![Trane CSRA025FAF0 Installation Operation & Maintenance Download Page 30](http://html1.mh-extra.com/html/trane/csra025faf0/csra025faf0_installation-operation-and-maintenance_1150303030.webp)
30
CSRA-SVX02A-EN
Installation
Figure 11 — Incorrect Vertical Hose Installation
Incorrect vertical hose installation shows an incorrect hose installation. In
this configuration the hose is installed without an elbow and with an
elevation greater than 7 feet off the ground. This creates excessive stress at
the hose coupling connection, causing the hose to stretch and separate from
the coupling. It also causes the hose to crimp at the ground.
The following figures illustrate the correct and incorrect methods for
installing hose in a horizontal and vertical combination application.
Figure 12 — Correct Horizontal/Vertical Installation
Correct horizontal/vertical installation shows a correct horizontal/vertical
hose installation. In this configuration, correct installation techniques
followed are:
• the hose is installed with elbows at both connection ends
• the vertical run of hose is less than 7 feet
• the hose is adequately supported by more than half its total length on
the ground
These items minimize the stretching and separation at the hose-coupling
interface and also the crimping of the hose at the ground.
Summary of Contents for CSRA025FAF0
Page 6: ...6 CSRA SVX02A EN General Information Figure 1a Model Number Description...
Page 18: ...18 CSRA SVX02A EN Installation Figure 4a C25 Ton Unit Dimensional Data Recommended Clearances...
Page 19: ...CSRA SVX02A EN 19 Installation Figure 4b C40 Ton Unit Dimensional Data Recommended Clearances...
Page 20: ...20 CSRA SVX02A EN Installation Figure 4c C60 Ton Unit Dimensional Data Recommended Clearances...
Page 47: ...CSRA SVX02A EN 47 Installation Figure 20A Typical Field Control Connections Diagram...
Page 48: ...48 CSRA SVX02A EN Installation Figure 20B Typical GBAS 0 5 Volt Connections Diagram...
Page 49: ...CSRA SVX02A EN 49 Installation Field Connection Diagram Notes for all System Control Options...
Page 65: ...CSRA SVX02A EN 65 System Start Up Figure 22 Condenser Fan Locations...