System Start-Up
Table 9 — Evaporator Data for C25 through C60 Units
Figure 21 — Evaporator Water Pressure Drop for CGAF-C20 through
C60 Units (English)
Note 1:
Factor to convert “Feet of Water” to “Lbs. per Sq. Inch” (PSI): 2.3
Feet of Water = 1 PSI
Unit Size
Water Volume
Minimum Flow Rate
Maximum Flow Rate
gal
liter
gpm
liter/s
gpm
liter/s
C60
37.8
143
72
4.5
216
13.6
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
45.00
0
50
100
150
200
250
Flow Rate (GPM)
Pressure Drop (Feet of Water)
C60 Ton
C25 Ton
C40 Ton