![Trane CSRA025FAF0 Installation Operation & Maintenance Download Page 51](http://html1.mh-extra.com/html/trane/csra025faf0/csra025faf0_installation-operation-and-maintenance_1150303051.webp)
CSRA-SVX02A-EN
51
System Pre-Start
Procedures
Note:
To avoid possible equipment damage, do not use untreated or
improperly treated system water.
Voltage Imbalance
Excessive three phase voltage imbalance between phases will cause motors
to overheat and eventually fail. The maximum allowable voltage imbalance is
2%. Measure and record the voltage between phases 1, 2, and 3 and
calculate the amount of imbalance as follows:
% Voltage Imbalance =
where;
AV (Average Voltage) =
V1, V2, V3 = Line Voltage Readings
VD = Line Voltage reading that deviates the farthest from the average
voltage.
Example: If the voltage readings of the supply power measured 221, 230,
and 227, the average volts would be:
VD (reading farthest from average) = 221
The percentage of Imbalance equals:
The 2.2% imbalance in this example exceeds the maximum allowable
imbalance of 2.0%. This much imbalance between phases can equal as
much as a 20% current imbalance with a resulting increase in motor winding
temperatures that will decrease motor life. If the voltage imbalance is over
2%, notify the proper agencies to correct the voltage problem before
operating this equipment.
Scroll Compressor Current Imbalance
Typically, current imbalance is associated with loss in motor efficiency,
higher operating motor temperature, loss of performance and reliability.
With the designs of specialized motors such as those used in the Trane
scroll compressor, operating temperature, efficiency, performance, and
reliability has been taken into account in the total performance of the
compressor.
Current imbalance in a scroll compressor can typically vary from 4 to 15
percent with balanced line voltage. This imbalance occurs because not all of
the winding turns see the same amount of stator iron. The variance of iron
within the motor is to accommodate design requirements for motor cooling
and oil return.
100
AV VD
–
AV
----------------------
Volt
1
Volt
2
Volt
3
+
+
3
--------------------------------------------------------
221 230 227
+
+
3
---------------------------------------
226
Avg
·
=
100226 221
–
226
------------------------
2.2
=
Summary of Contents for CSRA025FAF0
Page 6: ...6 CSRA SVX02A EN General Information Figure 1a Model Number Description...
Page 18: ...18 CSRA SVX02A EN Installation Figure 4a C25 Ton Unit Dimensional Data Recommended Clearances...
Page 19: ...CSRA SVX02A EN 19 Installation Figure 4b C40 Ton Unit Dimensional Data Recommended Clearances...
Page 20: ...20 CSRA SVX02A EN Installation Figure 4c C60 Ton Unit Dimensional Data Recommended Clearances...
Page 47: ...CSRA SVX02A EN 47 Installation Figure 20A Typical Field Control Connections Diagram...
Page 48: ...48 CSRA SVX02A EN Installation Figure 20B Typical GBAS 0 5 Volt Connections Diagram...
Page 49: ...CSRA SVX02A EN 49 Installation Field Connection Diagram Notes for all System Control Options...
Page 65: ...CSRA SVX02A EN 65 System Start Up Figure 22 Condenser Fan Locations...