Installation
Table 2B — Insulated, Non-Thermostatically Controlled Heat Tape with
Outer Wrap
Note:
Spiralled applications are twisted around pipe 3 turns per linear foot of
pipe.
Electrical Cable
Technical Data
Conductor Size: 2/0 AWG
Ampacity: 300 Amps per conductor*
Construction: Rope stranded copper conductor, colored-coded (blue, red,
green and black) connectors on each end. Insulation is
composed of water, acid, ozone and chemical resistant
thermoplastic rubber compound.
Temperature Rating (°F): -49 to 194
Weight (Lbs./100 Ft.): 64
Conductor Nominal OD (in.): 0.8200
Cable Rating: UL Rated at 2000 Volts, C(UL) 600 volts for continuous use.
*The values listed above are based upon ambient temperature @ 86 °F,
where the individual conductor is not installed in raceways or buried
(Reference NEC Code, Table 310-16, 1999 Edition).
Application
Technique “Straight”
Pipe Size
2”
2-1/2”
3”
4”
5”
Heat Tape Req. per Linear
Ft. of Pipe
12”
12”
12”
12”
12”
Protection Down to (°F)
-6°
0°
3°
12°
16°
“Spiralled”
Heat Tape Req. per Linear
Ft. of Pipe
26”
31”
35”
47”
54”
Protection Down to (°F)
-55°
-50°
-45°
-40°
-1°
Summary of Contents for CSRA025FAF0
Page 6: ...6 CSRA SVX02A EN General Information Figure 1a Model Number Description...
Page 18: ...18 CSRA SVX02A EN Installation Figure 4a C25 Ton Unit Dimensional Data Recommended Clearances...
Page 19: ...CSRA SVX02A EN 19 Installation Figure 4b C40 Ton Unit Dimensional Data Recommended Clearances...
Page 20: ...20 CSRA SVX02A EN Installation Figure 4c C60 Ton Unit Dimensional Data Recommended Clearances...
Page 47: ...CSRA SVX02A EN 47 Installation Figure 20A Typical Field Control Connections Diagram...
Page 48: ...48 CSRA SVX02A EN Installation Figure 20B Typical GBAS 0 5 Volt Connections Diagram...
Page 49: ...CSRA SVX02A EN 49 Installation Field Connection Diagram Notes for all System Control Options...
Page 65: ...CSRA SVX02A EN 65 System Start Up Figure 22 Condenser Fan Locations...