![Trane CSRA025FAF0 Installation Operation & Maintenance Download Page 23](http://html1.mh-extra.com/html/trane/csra025faf0/csra025faf0_installation-operation-and-maintenance_1150303023.webp)
CSRA-SVX02A-EN
23
Installation
5. Ensure that the compressor rail assembly is free to move on the rubber
isolators.
Figure 6 — Removing C25 through C60 Scroll Compressor Shipping
Hardware Installation
General Unit Requirements
The checklist listed below is a summary of the steps required to successfully
install a commercial air cooled unit. This checklist is intended to acquaint the
installing personnel with what is required in the installation process. It does
not replace the detailed instruction called out in the applicable sections of
this manual.
[ ] Verify that the power supply complies with the unit nameplate
specifications.
[ ] Check the unit for shipping damage and material shortage; file a freight
claim and notify Trane office.
[ ] Verify that the installation location of the unit will provide the required
clearance for proper operation.
Chilled Water Piping Requirements
[ ] Flushing the chilled solution piping system, if applicable.
CAUTION
Evaporator Damage!
If using an acidic, commercial flushing solution, flush all chilled solution
piping before making the final connection to the EVP chiller barrel.
Failure to do so may result in evaporator damage.
[ ] Install heat tape and insulation, if necessary, to protect any exposed
solution piping from external freezing conditions.
Summary of Contents for CSRA025FAF0
Page 6: ...6 CSRA SVX02A EN General Information Figure 1a Model Number Description...
Page 18: ...18 CSRA SVX02A EN Installation Figure 4a C25 Ton Unit Dimensional Data Recommended Clearances...
Page 19: ...CSRA SVX02A EN 19 Installation Figure 4b C40 Ton Unit Dimensional Data Recommended Clearances...
Page 20: ...20 CSRA SVX02A EN Installation Figure 4c C60 Ton Unit Dimensional Data Recommended Clearances...
Page 47: ...CSRA SVX02A EN 47 Installation Figure 20A Typical Field Control Connections Diagram...
Page 48: ...48 CSRA SVX02A EN Installation Figure 20B Typical GBAS 0 5 Volt Connections Diagram...
Page 49: ...CSRA SVX02A EN 49 Installation Field Connection Diagram Notes for all System Control Options...
Page 65: ...CSRA SVX02A EN 65 System Start Up Figure 22 Condenser Fan Locations...