CSRA-SVX02A-EN
Installation
Figure 15 — Typical Insulated, Spiralled Heat Tape Installation
Table 2A — Non-Insulated, Non-Thermostatically Controlled Heat Tape
with Outer Wrap
Note:
Spiralled applications are twisted around pipe 3 turns per linear foot of
pipe.
Application
Technique “Straight”
Pipe Size
2”
2-1/2”
3”
4”
5”
Heat Tape Req. per Linear
Ft. of Pipe
12”
12”
12”
12”
12”
Protection Down to (°F)
6°
11°
15°
20°
22°
“Spiralled”
Heat Tape Req. per Linear
Ft. of Pipe
28”
31”
35”
47”
54”
Protection Down to (°F)
-27°
-23°
-20°
-17°
-15°