37
CDHF-SVU01C-EN
Operator
Interface
Diagnostic Screen
The
diagnostic screen
is accessible
by touching the
Alarms
enunciator.
When an alarm is present, the alarm
enunciator is present next to the Stop
key. A flashing “alarm” indicates a
machine shutdown and a non
flashing “alarm” indicates an
informational message.
Machine shutdowns can be of two
types:
Latching - Machine Shutdown
Manual Reset Required (MMR)
or
Non-Latching - Machine Shutdown
Auto Reset (MAR)
Latching (MMR) require corrective
action and manual reset.
Non-Latching (MAR) will restart
automatically when condition
corrects itself.
There are over 200 potential
messages, too numerous to
incorporate in this manual.
Up to ten active diagnostics can be
displayed if required.
The reason for all diagnostics must
be determined and corrected. Do not
reset and restart the chiller as this
can cause a repeat failure. Contact
local Trane Service for assistance as
necessary.
After corrective action, the chiller can
be reset and/or restarted. In the case
of “Unit Shutdown - Reset Required”
diagnostic types, the chiller will have
to be manually reset through the
Diagnostics alarm menu.
When reset they become historic and
viewable via the service tool
TechView.
Performing a
Reset All Active
Diagnostics
will reset all active
diagnostics regardless of type,
machine or refrigerant circuit.
A
Manual Override
indicator (shares
space with the Alarms key) alerts the
operator to the presence of a manual
override. An Alarm will take
precedence over any manual
override, until the reset of active
alarms, at which point the Manual
indicator would reappear if such an
override exists.
Temperature settings
can be
expressed in F or C, depending on
Display Units settings.
Dashes (“- - - -”) appearing in a
temperature or pressure report,
indicates that the value is invalid or
not applicable.
The
languages
for DynaView
™
will
reside in the main processor. The
main processor will hold three
languages, English, and two alternate
languages. The service tool
(TechView
™
) will load the main
processor with user selected
languages from a list of available
translations. Whenever possible,
complete words will be used on the
persistent keys as described.
Summary of Contents for CenTraVac Duplex CDHE
Page 23: ...23 CDHF SVU01C EN General Information Figure 16 Oil refrigerant pump circuit 1 or 2 ...
Page 52: ...CDHF SVU01C EN 52 Control System Components Figure 24 Control panel components layout ...
Page 53: ...53 CDHF SVU01C EN Control System Components ...
Page 65: ...65 CDHF SVU01C EN Control System Components ...
Page 66: ...CDHF SVU01C EN 66 Control System Components ...
Page 104: ...CDHF SVU01C EN 104 ...
Page 105: ...105 CDHF SVU01C EN ...
Page 106: ...CDHF SVU01C EN 106 ...
Page 107: ...107 CDHF SVU01C EN ...
Page 108: ...CDHF SVU01C EN 108 ...
Page 109: ...109 CDHF SVU01C EN ...
Page 110: ...CDHF SVU01C EN 110 ...
Page 111: ...111 CDHF SVU01C EN ...
Page 112: ...CDHF SVU01C EN 112 ...
Page 113: ...113 CDHF SVU01C EN ...
Page 114: ...CDHF SVU01C EN 114 ...
Page 115: ...115 CDHF SVU01C EN ...