Head Relief Request Output
When the chiller is running in
Condenser Limit Mode or in Surge
Mode, the head relief request relay
on the 1A9–J2-6 to J2-4 will be
energized (1 minute default) and can
be used to control or signal for a
reduction in the entering condenser
water temperature. Designed to
prevent high refrigerant pressure trip-
outs during critical periods of chiller
operation.
If the unit is not equipped with the
CDPR Enhanced Condenser Limit
Option the unit will use the
condenser refrigerant temperature
sensor (input converted to saturated
refrigerant pressure) to perform the
Standard Condenser Limit function,
without the head relief request relay,
by limiting inlet guide vane stroke
and chiller capacity.
Keep in mind that Condenser Limit
Control supplements the protection
provided by the condenser pressure
high pressure cutout switch 3S1.
Motor Temperature sensor module
The motor temperature module 1A26
connects via unit wiring to the three
motor winding temperature sensors.
This module is located in the control
panel where the module is connected
to the IPC bus.
Default status relay selections are
shown. Selections can be altered
using service tool. Other choices are:
Circuit 1 Running, Circuit 2 Running,
Chiller Alarm, Circuit 1 Alarm, Circuit
2 Alarm, and Purge Alarm.
Maximum Capacity Relay
When the chiller has been operating
at maximum capacity for 10 minutes
(TechView adjustable) this relay will
activate. Also upon being less than
maximum capacity for 10 minutes
this relay will deactivate.
Compressor Running Relay
Relay activates while compressor is
running.
Machine Shutdown Manual
Reset (MMR)
Limit warning machine shutdown
auto reset relays will activate with
such conditions for remote status
indication.
Control System
Components
OPST Operation Status Option
Relay output modules 1A8 and 1A9 provide relay defaults shown (For other selections, see Installation Manual):
1A8 Optional Quad Relay
OPST
Relay #1
Chiller Non-Latching Alarm
J2-1 NO, J2-2 NC,
Output Status
J2-3 common
1A8 Optional Quad Relay
OPST
Relay #2
Chiller Limit
J2-4 NO, J2-5 NC,
Output Status
Mode Indicator
J2-6 common
1A8 Optional Quad Relay
OPST
Relay #3
Chiller Latching
J2-7 NO, J2-8 NC,
Output Status
Alarm Indicator
J2-9 common
1A8 Optional Quad Relay
OPST
Relay #4
Chiller Running Indicator
J2-10 NO, J2-11 NC,
Output Status
J2-12 common
1A9 Optional Quad Relay
OPST
Relay #1
Chiller Maximum Capacity
J2-1 NO, J2-2 NC,
Output Status
J2-3 common
1A9 Optional Quad Relay
OPST
Relay #2
Chiller Head
J2-4 NO, J2-5 NC,
Output Status
Relief Request
J2-6 common
1A9 Optional Quad Relay
OPST
Relay #3
Circuit 2
J2-4 NO, J2-5 NC
Output Status
Purge Alarm
to J2-6 common
1A9 Optional Quad Relay
OPST
Relay #4
Circuit 1
J2-1 NO, J2-2 NC,
Output Status
Purge Alarm
to J2-3 common
Chilled and Condenser Water
Flow Interlock Circuits
Proof of chilled water flow for the
evaporator is made by the closure of
flow switch 5S1 and the closure of
auxiliary contacts 5K1 on terminals
1X1-5 and 1A6-J3-2. Proof of
condenser water flow for the
condenser is made by the closure of
flow switch 5S2 and the closure of
auxiliary contacts 5K2 on terminals
1X1-6 and 1A6-J2-2.
Summary of Contents for CenTraVac Duplex CDHE
Page 23: ...23 CDHF SVU01C EN General Information Figure 16 Oil refrigerant pump circuit 1 or 2 ...
Page 52: ...CDHF SVU01C EN 52 Control System Components Figure 24 Control panel components layout ...
Page 53: ...53 CDHF SVU01C EN Control System Components ...
Page 65: ...65 CDHF SVU01C EN Control System Components ...
Page 66: ...CDHF SVU01C EN 66 Control System Components ...
Page 104: ...CDHF SVU01C EN 104 ...
Page 105: ...105 CDHF SVU01C EN ...
Page 106: ...CDHF SVU01C EN 106 ...
Page 107: ...107 CDHF SVU01C EN ...
Page 108: ...CDHF SVU01C EN 108 ...
Page 109: ...109 CDHF SVU01C EN ...
Page 110: ...CDHF SVU01C EN 110 ...
Page 111: ...111 CDHF SVU01C EN ...
Page 112: ...CDHF SVU01C EN 112 ...
Page 113: ...113 CDHF SVU01C EN ...
Page 114: ...CDHF SVU01C EN 114 ...
Page 115: ...115 CDHF SVU01C EN ...