85
CDHF-SVU01C-EN
Reset Ratio:
The Reset Ratio is displayed as a
percentage. To use it in the above
equation it must be converted to it’s
decimal form.
Reset Ratio percent /100 = Reset
Ratio decimal
Example of converting Reset Ratio:
If the Reset Ratio displayed on the
CLD is 50 percent then use (50/100)=
.5 in the equation
TOD
= Outdoor Air Temperature
Start Reset
= Outdoor Air Start Reset
Example of Calculating Reset for
Outdoor Air Temperature:
If:
Reset Ratio = 35 percent
Start Reset = 80
TOD = 65
Maximum Reset = 10.5
How many Degrees of Reset will
there be?
Degrees of Reset = Reset Ratio*(Start
Reset - TOD)
Degrees of Reset = .35*(80-65)
Degrees of Reset = 5.25
(* = multiply)
If:
Reset Ratio = -70 percent
Start Reset = 90
TOD = 100
Maximum Reset = 17
How many Degrees of Reset will
there be?
Degrees of Reset = Reset Ratio* (Start
Reset - TOD)
Degrees of Reset = -7* (90-100)
Degrees of Reset = 7
Figure 32. Outdoor air temperature versus degrees of reset
Machine Protection
and Adaptive
Control
Summary of Contents for CenTraVac Duplex CDHE
Page 23: ...23 CDHF SVU01C EN General Information Figure 16 Oil refrigerant pump circuit 1 or 2 ...
Page 52: ...CDHF SVU01C EN 52 Control System Components Figure 24 Control panel components layout ...
Page 53: ...53 CDHF SVU01C EN Control System Components ...
Page 65: ...65 CDHF SVU01C EN Control System Components ...
Page 66: ...CDHF SVU01C EN 66 Control System Components ...
Page 104: ...CDHF SVU01C EN 104 ...
Page 105: ...105 CDHF SVU01C EN ...
Page 106: ...CDHF SVU01C EN 106 ...
Page 107: ...107 CDHF SVU01C EN ...
Page 108: ...CDHF SVU01C EN 108 ...
Page 109: ...109 CDHF SVU01C EN ...
Page 110: ...CDHF SVU01C EN 110 ...
Page 111: ...111 CDHF SVU01C EN ...
Page 112: ...CDHF SVU01C EN 112 ...
Page 113: ...113 CDHF SVU01C EN ...
Page 114: ...CDHF SVU01C EN 114 ...
Page 115: ...115 CDHF SVU01C EN ...