CDHF-SVU01C-EN
74
Current Limit Protection
Current Limit Protections exist to
avoid motor current overload and
damage to the compressor motor
during starting and running.
Compressor motor current is
continuously monitored and current
is controlled via a limit function that
to prevent running into over current
diagnostic trips.
The current limit control logic
attempts to prevent the motor from
shutting down on a diagnostic trip by
limiting compressor current draw
relative to an adjustable current limit
DynaView
™
Current Limit Setpoint.
This setpoint can also be lowered to
provide electrical demand limiting on
the unit as required. This could also
be set to allow the Chiller to continue
to run at a lower load to avoid
tripping off via a diagnostic.
The Current Limit function uses a PID
algorithm (Similar to the Leaving
Water Temperature control) that
allows the chiller to run at the
Current Limit Setpoint. At machine
startup, or with any setpoint change
the new current limit setpoint
reached after the is filtered setpoint
time elapses. The minimum current
limit setpoint is default set to 40
percent RLA (20-100 percent). The
filtering time is default set to 10
minutes (0-120 minutes), however
these can be altered via the service
tool. This filtered setpoint allows for
stable control if the Current Limit
setpoint is adjusted during a run.
The Current Limit Setpoint (CLS) can
be changed from: Front Panel,
External Analog input (with GBAS
(external) option), or Tracer (Tracer
option). However, If present Tracer
current setpoint has the highest
priority, unless disabled in the
DynaView
™
Setpoint source override
menu. The External CLS has second
priority, and will be used if Tracer is
disabled or not installed. The Front
Panel Setpoint has the lowest
priority, and will be used if Tracer
and the External CLS are both
disabled.
Phase Loss Protection
Loss of phase detection protects the
chiller motor from damage due to a
single-phasing condition. The
controls will shut down the chiller if
any of the three phase currents
feeding the motor are lost. The
shutdown will result in a latching
diagnostic indicating the failure. The
motor is protected from over-current
during a single-phase condition by
the Current Overload Protection
feature. Phase Loss Protection
provides redundant protection and a
diagnostic that more accurately
describes the fault.
Reverse Rotation Protection
This function protects the
compressor from being driven in the
reverse direction. Incorrect phase
rotation detection results in a
manually resettable diagnostic.
Phase Reversal protection is default
to Enable, however can be disabled
via the service tool.
Machine Protection
and Adaptive
Control
Summary of Contents for CenTraVac Duplex CDHE
Page 23: ...23 CDHF SVU01C EN General Information Figure 16 Oil refrigerant pump circuit 1 or 2 ...
Page 52: ...CDHF SVU01C EN 52 Control System Components Figure 24 Control panel components layout ...
Page 53: ...53 CDHF SVU01C EN Control System Components ...
Page 65: ...65 CDHF SVU01C EN Control System Components ...
Page 66: ...CDHF SVU01C EN 66 Control System Components ...
Page 104: ...CDHF SVU01C EN 104 ...
Page 105: ...105 CDHF SVU01C EN ...
Page 106: ...CDHF SVU01C EN 106 ...
Page 107: ...107 CDHF SVU01C EN ...
Page 108: ...CDHF SVU01C EN 108 ...
Page 109: ...109 CDHF SVU01C EN ...
Page 110: ...CDHF SVU01C EN 110 ...
Page 111: ...111 CDHF SVU01C EN ...
Page 112: ...CDHF SVU01C EN 112 ...
Page 113: ...113 CDHF SVU01C EN ...
Page 114: ...CDHF SVU01C EN 114 ...
Page 115: ...115 CDHF SVU01C EN ...