CDHF-SVU01C-EN
32
Operator
Interface
The
Auto
and
Stop
keys are used to
put the unit into the auto or stop
modes. Key selection is indicated by
being darkened (reverse video).
The
Alarms
button is to the right of
the
Stop
key. The
Alarms
button
appears only when alarm information
is present. The alarm blinks to draw
attention to the shutdown diagnostic
condition. Blinking is defined as
normal versus reverse video.
Pressing on the
Alarms
button takes
you to the corresponding screen.
Persistent keys
, horizontal at the
bottom of the display, are those keys
that must be available for operation
regardless of the screen currently
being displayed. These keys are
critical for machine operation. The
Auto and Stop
keys will be
presented as radio buttons within the
persistent key display area. The
selected key will be dark. The chiller
will stop when the
Stop
key is
touched, entering the stop sequence.
Pressing the “Immediate Stop”
button will cause the chiller to stop
immediately.
The AUTO and STOP, take
precedence over the ENTER and
CANCEL keys. (While a setting is
being changed, AUTO and STOP
keys are recognized even if ENTER or
CANCEL has not been pressed.
Selecting the Auto key will enable the
chiller for active cooling ( if no
diagnostic is present.)
Chiller Stop Prevention/Inhibit
Feature
A new chiller “Stop prevention/
inhibit” feature allows a user to
prevent an inadvertent chiller stop
from the DynaView screen for those
chillers which are solely controlled
by the CH530.
How It Works
This new feature will be activated
after the service tech sets a variable
shut down timer in TechView to be
greater that 0 seconds and up to 20
seconds (i.e. 0 < Timer ± 20). Then,
when the user presses the ‘STOP’
button on the DynaView display and
initiates a chiller shutdown, a
window will now appear that
displays the “Unit Stop Information
Screen” as shown below.
TechView service tool is utilized to
enable this feature.
Summary of Contents for CenTraVac Duplex CDHE
Page 23: ...23 CDHF SVU01C EN General Information Figure 16 Oil refrigerant pump circuit 1 or 2 ...
Page 52: ...CDHF SVU01C EN 52 Control System Components Figure 24 Control panel components layout ...
Page 53: ...53 CDHF SVU01C EN Control System Components ...
Page 65: ...65 CDHF SVU01C EN Control System Components ...
Page 66: ...CDHF SVU01C EN 66 Control System Components ...
Page 104: ...CDHF SVU01C EN 104 ...
Page 105: ...105 CDHF SVU01C EN ...
Page 106: ...CDHF SVU01C EN 106 ...
Page 107: ...107 CDHF SVU01C EN ...
Page 108: ...CDHF SVU01C EN 108 ...
Page 109: ...109 CDHF SVU01C EN ...
Page 110: ...CDHF SVU01C EN 110 ...
Page 111: ...111 CDHF SVU01C EN ...
Page 112: ...CDHF SVU01C EN 112 ...
Page 113: ...113 CDHF SVU01C EN ...
Page 114: ...CDHF SVU01C EN 114 ...
Page 115: ...115 CDHF SVU01C EN ...