CDHF-SVU01C-EN
38
Operator
Interface
The
chilled water reset status
area in
the right most column will display
one of the following messages:
Return, Constant Return, Outdoor,
None
The left column text “Front Panel”,
“BAS”, “External”, Chilled Water
Reset, and “Active Chilled Water
Setpoint” will always be present
regardless of installation or enabling
those optional items. In the second
column “- - - -” will be shown if that
option is Not Installed, otherwise the
current setpoint from that source will
be shown.
The
“Back” button
provides
navigation back to the chiller screen.
The
active chilled water setpoint
is
the setpoint that is currently in use. It
will be displayed to 0.1 degrees
Fahrenheit or Celsius. Touching
the
double arrow
to the left of the Active
Chilled Water Setpoint will take the
user to the active chilled water
setpoint arbitration sub-screen.
The Active Chilled Water Setpoint
the result of arbitration between the
front panel, BAS, and external
setpoints,
Summary of Contents for CenTraVac Duplex CDHE
Page 23: ...23 CDHF SVU01C EN General Information Figure 16 Oil refrigerant pump circuit 1 or 2 ...
Page 52: ...CDHF SVU01C EN 52 Control System Components Figure 24 Control panel components layout ...
Page 53: ...53 CDHF SVU01C EN Control System Components ...
Page 65: ...65 CDHF SVU01C EN Control System Components ...
Page 66: ...CDHF SVU01C EN 66 Control System Components ...
Page 104: ...CDHF SVU01C EN 104 ...
Page 105: ...105 CDHF SVU01C EN ...
Page 106: ...CDHF SVU01C EN 106 ...
Page 107: ...107 CDHF SVU01C EN ...
Page 108: ...CDHF SVU01C EN 108 ...
Page 109: ...109 CDHF SVU01C EN ...
Page 110: ...CDHF SVU01C EN 110 ...
Page 111: ...111 CDHF SVU01C EN ...
Page 112: ...CDHF SVU01C EN 112 ...
Page 113: ...113 CDHF SVU01C EN ...
Page 114: ...CDHF SVU01C EN 114 ...
Page 115: ...115 CDHF SVU01C EN ...