CDHF-SVU01C-EN
98
Maintenance
DO NOT LEAVE GREASE FITTINGS
INSTALLED.
If grease fittings have been used for
this procedure then they MUST BE
REMOVED before returning the unit
to service. Grease fittings are not
vacuum-tight and will become a leak
path.
9. Using a clean wooden dowel or
other similar tool, remove excess
grease from the remaining open
lubrication port.
10. Clean and then lightly coat the
threads of the plug with Rheolube
grease and re-install it into the
lubrication port. Tighten the
plug to hand tight plus 1/4 to 1/2
turn.
11. Before reconnecting the vane
linkage, grasp the tang operator
arm and manually operate the
vane assembly. If it is now
difficult to move, then the tang
operator may have become
“hydraulically locked” because of
excess grease in the assembly.
This situation could cause
damage to the o-rings of the
assembly. If this occurs then
remove one of the lubrication
plugs, remove some of the
grease, then re-install the plug.
12. Reconnect the linkage to the tang
operator arm. Ensure the spacer
washers between the linkage and
the arm are properly placed and
that the assembly does not bind.
Re-install any insulation that was
cut or removed. The unit may be
restarted.
To service the 1st and 2nd stage tang
operators on CDHF extended
capacity chillers with 1470 or 1720
compressors.
The 1st and 2nd stage rotary inlet
guide vane tang operators of the
extended capacity chillers also
require periodic lubrication, at least
annually, with R123 compatible
Rheolube grease. These actuators
have two 1/8" NPT plugs located 180
degrees apart, with one on the top
Figure 37. Rotary valve in drain position
Front View with Refrigerant Pump
and the other on the bottom of the
operator base. Use the same
procedure as described above,
except that it will be necessary to
temporarily disconnect the vane
actuators from the tang operator
arms in order to test for a
“hydraulically locked” condition.
The oil valve block rotary valve uses
dual O-Rings to seal to atmosphere.
These should be manually lubricated
by removing the pipe plug at the
valve lubrication port and placing a
few drops of Trane OIL00022 in the
cavity. Be sure to reinstall the pipe
plug when lubrication is completed.
Summary of Contents for CenTraVac Duplex CDHE
Page 23: ...23 CDHF SVU01C EN General Information Figure 16 Oil refrigerant pump circuit 1 or 2 ...
Page 52: ...CDHF SVU01C EN 52 Control System Components Figure 24 Control panel components layout ...
Page 53: ...53 CDHF SVU01C EN Control System Components ...
Page 65: ...65 CDHF SVU01C EN Control System Components ...
Page 66: ...CDHF SVU01C EN 66 Control System Components ...
Page 104: ...CDHF SVU01C EN 104 ...
Page 105: ...105 CDHF SVU01C EN ...
Page 106: ...CDHF SVU01C EN 106 ...
Page 107: ...107 CDHF SVU01C EN ...
Page 108: ...CDHF SVU01C EN 108 ...
Page 109: ...109 CDHF SVU01C EN ...
Page 110: ...CDHF SVU01C EN 110 ...
Page 111: ...111 CDHF SVU01C EN ...
Page 112: ...CDHF SVU01C EN 112 ...
Page 113: ...113 CDHF SVU01C EN ...
Page 114: ...CDHF SVU01C EN 114 ...
Page 115: ...115 CDHF SVU01C EN ...