WX9 ASD Installation and Operation Manual
105
RX Reference Point 1
Program
Torque
Setpoints
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the
RX
input
terminal when this
terminal is used as the control input while operating in the
Speed Control
or the
Torque Control
mode.
This parameter sets the
RX
input level that represents
RX Reference Setpoint
1
(direction/torque/frequency).
The input signal may be trimmed using
(bias) and
(gain).
RX Speed Control Setup
Perform the following setup to allow the system to receive control input at the
RX
input terminal:
•
Program
Fundamental Parameters
Standard Mode Selection
Frequency Mode 1
RX
.
•
Program
Fundamental Parameters
Standard Mode Selection
Command Mode Selection
Terminal Board
.
•
Set
RX Point 1 Frequency
(
)
.
•
Set
RX Reference Point 1
) — the input analog signal level that
corresponds to the speed setting at
RX Point 1 Frequency
.
•
Set
RX Point 2 Frequency
(
)
.
•
Set
RX Reference Point 2
) — the input analog signal level that
corresponds to the speed setting at
RX Point 2 Frequency
.
•
Provide a
Run
command (F or R).
When operating in the
Torque Control
mode, the settings that determine the
direction, gain, and bias of the
RX
terminal are:
•
RX Input Point 1 Torque
(
)
,
•
the
RX
input signal level that represents the
RX Reference Point 1
(
•
RX Input Point 2 Torque
(
)
, and
•
the
RX
input signal level that represents the
RX Reference Point 2
(
Once set, as the
RX
input voltage changes, the directional information, the
output frequency, or the output torque of the drive will vary in accordance with
the above settings.
This parameter value is entered as -100 to +100% of the -10 to +10 VDC
RX
input signal range.
Direct Access Number — F216
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -100.0
Maximum — 100.0
Units — %
Frequency Settings
RX Point 1 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the
RX
input
terminal when this
terminal is used as the control input while operating in the
Speed Control
mode.
See
RX Reference Point 1
for additional information on this setting.
This parameter sets
RX Point 1 Frequency
and is the frequency that is
associated with the setting of
RX Reference Point 1
Direct Access Number — F217
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — - (Maximum Freq. (
Maximum — + (Maximum Freq. (
))
Units — Hz