106
WX9 ASD Installation and Operation Manual
RX Reference Point 2
Program
Torque
Setpoints
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the
RX
input
terminal when this terminal is used as the control input while operating in the
Speed Control
or the
Torque Control
mode.
This parameter sets the
RX
input level that represents
RX Reference Point 2
(frequency)
(direction/torque/frequency). The range of values for this parameter
is -100 to +100% of the -10 to +10 VDC
RX
input signal range.
See
RX Reference Point 1
for additional information on this setting.
Direct Access Number — F218
Parameter Type —
Numerical
Factory Default — +
100.0
Changeable During Run —
Yes
Minimum — -100.0
Maximum — +100.0
Units — %
RX Point 2 Frequency
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the
RX
input
terminal when this
terminal is used as the control input while operating in the
Speed Control
mode.
This parameter sets
RX Point 2 Frequency
and is the frequency that is
associated with the setting of
RX Reference Point 2
See
RX Reference Point 1
for additional information on this setting.
Direct Access Number — F219
Parameter Type —
Numerical
Factory Default — +
60.0
Changeable During Run —
Yes
Minimum — - (Maximum Freq. (
Maximum — + (Maximum Freq. (
))
Units — Hz
RX Input Point 1 Torque
Program
Torque
Setpoints
This parameter is used to set the direction, gain, and bias of the
RX
input
terminal when this
terminal is used as the control input while operating in the
Torque Control
mode.
The bias and gain of the RX terminal may be trimmed at
,
respectively.
RX Torque Control Setup
Perform the following setup to allow the system to receive Torque Control
input at the RX input terminal:
•
Program
Fundamental
Standard Mode Selection
Frequency
Mode
RX
•
Program
Fundamental
Standard Mode Selection
Command
Mode Selection
Terminal Board
•
Set
RX Input Point 1 Torque
(
).
•
Set
RX Reference Point 1
(
) — the input analog signal level that
corresponds to the torque setting at
RX Input Point 1 Torque
.
•
Set
RX Input Point 2 Torque
(
).
•
Set
RX Reference Point 2
(
) — the input analog signal level that
corresponds to the speed setting at
RX Input Point 2 Torque
.
•
Provide a
Run
command (
F
and/or
R
).
Torque Control
is accomplished by establishing an associated V/f output
pattern for a given
RX
input level.
Once set, as the
RX
input voltage changes, the ASD output speed and/or torque
will vary in accordance with the above settings.
This parameter sets
RX
Input Point 1 Torque
and is the output torque value
that is associated with the setting of
RX Reference Point 1
This value is entered as -250 to +250% of the rated torque.
Direct Access Number — F220
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -250.0
Maximum — +250.0
Units — %
Torque Settings