WX9 ASD Installation and Operation Manual
107
RX Input Point 2 Torque
Program
Torque
Setpoints
This parameter is used to set the direction, gain, and bias of the
RX
input
terminal when this
terminal is used as the control input while operating in the
Torque Control
mode.
Torque Control
is accomplished by establishing an associated V/f output
pattern for a given
RX
input level.
This parameter sets
RX
Input Point 2 Torque
and is the output torque value
that is associated with the setting of
RX Reference Point 2
). This value
is entered as -250 to +250% of the rated torque.
See
RX Input Point 1 Torque
(
)
for additional information on this
setting.
Direct Access Number — F221
Parameter Type —
Numerical
Factory Default — +
100.0
Changeable During Run —
Yes
Minimum — -250.0
Maximum — +250.0
Units — %
RX2 Reference Point 1
Program
Torque
Setpoints
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the
RX2
input
terminal when this
terminal is used as the control input while operating in the
Speed Control
or the
Torque Control
mode.
Note:
The
Expansion IO Card Option 1
option board (P/N ETB003Z)
is required to use this terminal.
This parameter sets the
RX2
input level that represents
RX2 Reference
Setpoint 1
(frequency) (direction/torque/frequency).
The input signal may be trimmed using
(bias) and
(gain).
RX2 Speed Control Setup
Perform the following setup to allow the system to receive control input at the
RX2
input terminal:
•
Program
Fundamental
Standard Mode Selection
Frequency
Mode 1
RX2
.
•
Program
Fundamental
Standard Mode Selection
Command
Mode Selection
Terminal Board
.
•
Set
RX2 Point 1 Frequency
(
•
Set
RX2 Reference Point 1
) — the input analog signal level
that corresponds to the speed setting at
RX2 Point 1 Frequency.
•
Set
RX2 Point 2 Frequency
(
•
Set
RX2 Reference Point 2
) — the input analog signal level
that corresponds to the speed setting at
RX Point 2 Frequency
.
•
Provide a
Run
command (F or R).
Once set, as the
RX2
voltage changes, the directional information, the output
frequency, or the output torque of the drive will vary in accordance with the
above settings.
This parameter value is entered as -100 to +100% of the
RX2
signal range.
See the
Expansion IO Card Option 1
instruction manual (P/N 58685) for
additional information on the function of this terminal.
Direct Access Number — F222
Parameter Type —
Numerical
Factory Default —
0.0
Changeable During Run —
Yes
Minimum — -100.0
Maximum — 100.0
Units — %
Frequency Settings